1. Specifications
1-11 Increasing the Fan Speed
Electrical component box
If external static pressure is too great (due to long | Fan |
|
| Jumper cable | ||||||||||
extension of ducts, for example), the air flow volume |
|
| ||||||||||||
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
| |||||
motor |
|
|
|
|
|
|
|
|
|
| ||||
may drop too low at each air outlet. This problem may |
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
be solved by increasing the fan speed using the |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Fan motor socket | ||||||||||
following procedure: |
|
|
|
| ||||||||||
|
|
|
|
| (At shipment) |
Jumper cable
(Jumper cable installed)
2159_M_I
(1)Remove 4 screws on the electrical component box and remove the cover plate.
(2)Disconnect the fan motor sockets in the box.
(3)Take out the jumper cable (sockets at both ends) clamped in the box.
(4)Securely connect the jumper cable sockets between the disconnected fan motor sockets in step 2.
(5)Place the cable neatly in the box and reinstall the cover plate.
External Static Pressure
150
(Pa)
100
50
12 Type
line |
| |
Limit | line | |
Limit | ||
| ||
| HT | |
| HH | |
| H | |
| L |
(inAq) | 150 |
| |
0.5 | (Pa) |
0.4Pressure 100
0.3 | Static |
|
0.2External 50
0.1
18 Type
Limit | line | |
line | ||
Limit | ||
|
HT
HH
H
L
(inAq)
0.5
0.4
0.3
0.2
0.1
0
200 | 300 | 400 |
Air Flow (CFM)
0 | 0 |
|
|
|
| 0 |
|
|
|
| |||
| 200 | 300 | 400 | 500 |
Air Flow (CFM)
Indoor Fan Performance |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 1980_U_I | |||||||||||
|
|
| 24 Type |
|
|
|
| 200 |
|
|
|
| 36 Type |
|
|
|
|
| 0.8 | |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
| (Pa) |
|
|
|
|
|
|
|
|
|
|
|
|
|
| (inAq) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
| (inAq) |
|
|
|
| line |
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| 150 | line |
|
|
|
|
|
|
|
| 150 |
|
| Limit |
|
|
|
|
|
|
|
|
|
| 0.6 | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
PressureStaticExternal | (Pa) | Limit |
|
|
|
|
|
|
|
| 0.5 | PressureStaticExternal |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 0.5 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
| 100 |
|
|
|
|
|
|
|
|
| 0.4 |
| 100 |
|
|
|
| line |
|
|
|
|
|
|
|
| 0.4 | |
|
| line |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
| Limit |
|
|
|
|
|
|
|
|
|
|
|
|
| Limit |
|
|
|
|
|
|
|
|
|
| 0.3 | |
|
|
|
|
|
|
|
|
|
| 0.3 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| HT |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 50 |
|
|
|
|
|
|
|
|
| 0.2 |
| 50 |
|
|
|
|
|
|
|
|
|
|
| HT |
|
| 0.2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| HH |
|
|
|
|
|
|
|
|
|
|
|
|
|
| H | H |
|
|
| |
|
|
|
|
|
| H |
|
|
|
| 0.1 |
|
|
|
|
|
|
|
|
|
| H |
|
|
|
|
| 0.1 |
|
|
|
|
| L |
|
|
|
|
|
|
|
|
|
|
|
|
|
| L |
|
|
|
|
|
|
|
|
| 0 |
|
|
|
|
|
|
|
|
| 0 |
| 0 |
|
|
|
|
|
|
|
|
|
|
|
|
|
| 0 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
| 300 | 500 |
| 700 | 900 |
| 500 |
|
|
| 1000 |
|
|
|
|
|
| |||||||||||
|
|
| Air Flow (CFM) |
|
|
|
|
|
|
|
|
| Air Flow (CFM) |
|
|
|
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
| 1982_U_I |
|
|
|
|
|
|
|
|
|
|
|
|
| 1983_U_I | |||
| NOTE |
|
| HT | : Using the booster cable |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
H : At shipment
1981_U_I
■How to read the diagram
The vertical axis is the external static pressure (Pa) while the horizontal axis represents the AIR FLOW (CFM). The characteristic curves for “HT”, “H”, “M” and “L” fan speed control are shown.
The nameplate values are shown based on the “H” air flow. For the 24 type, the air flow is 636 CFM, while the external static pressure is 49 Pa at “H” position. If external static pressure is too great (due to long extension of duct, for example), the air flow volume may drop too low at each air outlet.
This problem may be solved by increasing the fan speed as explained above.
SM830082