Sanyo UH3642 / CH3642 Installation Instructions Tubing Length, Models CH2442, Tubing Data

Models: TH4242 / CH4242 XH2442 / CH2442 XH3642 / CH3642 KH2442 / CH2442 UH3642 / CH3642 TH2442 / CH2442 UH2442 / CH2442 TH3642 / CH3642 KH3642 / CH3642 XH4242 / CH4242

1 202
Download 202 pages 41.27 Kb
Page 103
Image 103

1-13 Installation Instructions

Tubing Length

Refrigerant tubing between the indoor and

outdoor units should be kept as short as possible.

Select and decide the installation location so that the length of the refrigerant tubing will be within the limits given in Table 1-10.

1. Specifications

 

INDOOR

 

Tubing length (L)

 

UNIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Elevation difference (H)

 

OUTDOOR

 

 

 

 

 

 

UNIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0711_M_I

Fig. 1-1

Table 1-10

 

 

 

Models

CH2442

CH3642, CH4242

Tubing Data

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Tubing size

 

Narrow tube

in. (mm)

1/4 (6.35)

3/8 (9.52)

outer dia.

Wide tube

in. (mm)

3/4 (19.05)

3/4 (19.05)

 

 

 

 

 

 

Limit of tubing length

 

 

(ft.)

165

165

 

 

 

 

 

Limit of elevation

Outdoor unit is higher

165

165

than indoor unit

(ft.)

difference between

 

 

 

 

 

 

 

 

 

 

Outdoor unit is lower

 

 

the 2 units

100

100

than indoor unit

 

 

(ft.)

 

Max. allowable tubing length at shipment (ft.)

100

100

 

 

 

 

 

Required additional refrigerant

 

(oz./ft.)

0.48*1

0.53*2

No additional charge of compressor oil is necessary.

*1

If total tubing length becomes 100 to 165 ft., charge additional refrigerant (R22) by 0.48 oz./ft..

*2

If total tubing length becomes 100 to 165 ft., charge additional refrigerant (R22) by 0.53 oz./ft..

1

SM830082

I - 99

Page 103
Image 103
Sanyo UH3642 / CH3642, XH3642 / CH3642, XH4242 / CH4242 Installation Instructions Tubing Length, Models CH2442, Tubing Data