4. Service procedures
10)Symptom: LCD on the remote controller displays “CHECK P02”. (Compressor / outdoor fan protection thermostat operation warning / power supply voltage
abnormality)
Start
Is the power supply to the outdoor No unit normal?
(Voltage / defective phase?)
Yes
Yes
Is the fuse on the outdoor unit PCB blown (F1 and F2)?
No
Yes
Is the high pressure switch (63 PH) off?
No
Yes
Is there
No
Check the power breaker etc. and repair.
Replace the fuse.
Replace the outdoor unit PCB.
Replace the outdoor unit PCB.
Is the outdoor fan wire winding | No |
protection thermostat (49FO) off?
Yes
4
•No refrigerant
•High load
•
•Clogged refrigerant circuit
•Electronic refrigerant control valve defect (indoor unit)
Replace the outdoor fan.
Yes
Is there connector contact defect? |
| Correct the connection |
|
No
Replace the outdoor unit PCB.
2099_THS_I
SM830082
IV - 14