4. Service procedures

(5) PCB Setting

Setting of outdoor control PCB

(A)Standard control (single outdoor unit)

In case of single outdoor unit installation, even if in case of twin, triple or quartet type (2, 3 or 4 indoor units), no setting necessary.

Keep factory shipment state (R.C. address is set in “0”).

In this case, auto. address operation takes place automatically for the first time when the power is switched on. This takes about a few minutes.

(B)Group control (Multiple outdoor units)

In case of group control (up to 8 indoor units can be connected with one remote controller), before turning the power supply on set the R.C. address with S2, S3 on the outdoor control PCB.

R.C. address: Refrigerant circuit address 1 ~ 30.

(C)Central control (when using the system controller)

In case of central control (when using the system controller,that is, when linking outdoor units in a network),

(a)Before turning the power supply on, set the R.C. address with S2, S3 on the outdoor control PCB.

(b)Remove the short plug (CN006, 2P Black) from all outdoor units except any one of outdoor unit.

Setting of indoor control PCB No setting necessary.

Each indoor unit address (UNIT No.: R.C. – No.) is decided after auto. address operation.

Indoor unit No.

Refrigerant Circuit No. (R.C. address)

Manual setting for indoor unit address can be performed also by remote controller.

SM830082

IV - 36

Page 192
Image 192