ELECTRICAL WIRING

General Precautions on Wiring

(1)Before wiring, confirm the rated voltage of the unit as shown on its nameplate, then carry out the wiring closely following the wiring diagram.

(2)Provide a power outlet to be used exclusively for each unit, and a power supply disconnect and circuit breaker for overcurrent protection should be provided in the exclusive line.

(3)To prevent possible hazards from insulation failure, the unit must be grounded.

(4)Each wiring connection must be done in accor- dance with the wiring system diagram. Wrong wiring may cause the unit to misoperate or become damaged.

(5)Do not allow wiring to touch the refrigerant tubing, compressor, or any moving parts of the fan.

(6)Unauthorized changes in the internal wiring can be very dangerous. The manufacturer will accept no responsibility for any damage or misoperation that occurs as a result of such unauthorized changes.

1. Specifications

(7)Regulations on wire diameters differ from locality to locality. For field wiring rules, must follow your LOCAL ELECTRICAL CODES before beginning.

You must ensure that installation complies with all relevant rules and regulations.

(8)To prevent malfunction of the air conditioner caused by electrical noise, care must be taken when wiring as follows:

The remote control wiring and the inter-unit control wiring should be wired apart from the inter-unit power wiring.

Use shielded wires for inter-unit control wiring between units and ground the shield on both sides.

(9)If the power supply cord of this appliance is damaged, it must be replaced by a repair shop appointed by the manufacture, because special purpose tools are required.

(10)All wiring must be used class 1.

Recommended Wire Length and Wire Diameter for Power Supply System

Must follow LOCAL ELECTRICAL CODES for wiring.

Outdoor Unit

 

 

 

 

 

 

* AWG = American Wire Gauge

Model Name

 

 

(A) Power Supply

 

Trade size

MOP

Power Supply Terminal Base

Trade size

 

 

 

 

of Conduit

(Fuse or HACR

 

 

 

of Conduit

 

 

 

 

 

 

 

type circuit braker)

Capacity

Max. Wire Diameter

 

 

 

 

 

 

 

 

 

 

 

 

 

CH2442

 

 

AWG #12

 

3/4 in.

25 A

50 A

AWG #6

1-1/4 in.

 

 

Max. length 69 ft.

 

 

 

 

 

 

 

 

 

 

 

 

CH3642

 

 

AWG #12

 

3/4 in.

35 A/40 A (230/208 V)

50 A

AWG #6

1-1/4 in.

 

 

Max. length 69 ft.

 

 

 

 

 

 

 

 

 

 

 

 

CH4242

 

 

AWG #10

 

3/4 in.

45 A

50 A

AWG #6

1-1/4 in.

 

 

Max. length 67 ft.

 

 

 

 

 

 

 

 

 

 

 

 

Indoor Unit

 

 

 

 

 

 

 

 

 

 

Type

 

 

(B) Power Supply

 

Trade size

MOP

Power Supply Terminal Base

Trade size

 

 

 

(Fuse or HACR

 

 

 

 

of Conduit

 

 

 

of Conduit

 

 

 

 

 

 

type circuit braker)

Capacity

Max. Wire Diameter

X, K, T, U

Max. length 330 ft.

 

3/4 in.

15 A

25 A

AWG #10

3/4 in.

 

 

 

 

 

 

 

 

 

 

 

Control Wiring

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(C) Inter-Unit Control Wiring

 

(D) Remote Control Wiring

 

(E) Control Wiring For Group Control

 

 

 

 

 

 

 

 

 

AWG #18 (0.75 mm2)

 

AWG #18* (0.75 mm2)

 

 

AWG #18*2 (0.75 mm2)

Use high voltage wire (300 V)*1

 

 

 

 

 

 

 

Max. 3,300 ft.

 

Max. 1,650 ft.

 

 

Max. 1,650 ft. (Total)

 

 

 

 

 

 

 

 

 

NOTE

 

*1

With ring type wire terminal.

 

 

 

 

 

 

 

*2

Wire joint connection.

 

 

 

 

 

SM830082

I - 104

Page 108
Image 108
Sanyo KH3642 / CH3642, XH3642 / CH3642, XH4242 / CH4242 General Precautions on Wiring, Use high voltage wire 300 V *1