1. Specifications

Outdoor Unit

AVOID:

heat sources, exhaust fans, etc. (Fig. 2-1)

damp, humid or uneven locations.

DO:

Hot air

Out- door unit

Exhaust fan

Heat source

0591_C_I

choose a place as cool as possible.

choose a place that is well ventilated and outside air temperature does not exceed maximum 115°F

constantly.

allow enough room around the unit for air intake/ exhaust and possible maintenance. (Fig. 2-2)

provide a solid base; about 6 inch above ground level to reduce humidity and possible water damage in the unit and decreased service life. (Fig. 2-3)

use lug bolts or equivalent to bolt down unit, reducing vibration and noise.

Min.

1 inch

Fig. 2-1

Min.

Obstacle above

1 inch

 

 

Min.

4 in.

7 ft.

 

Air

 

dis-

 

charge

Min. 2 ft.

 

0931_C_I

Ground

 

 

0932_C_I

1

Fig. 2-2

In case of multiple installations

Unit spacing if air discharge chamber is not used.

 

Unit spacing when air discharge chamber is used.

Min. 4 ft.

Min. 5 ft.

Min. 4 ft.

Min. 4 ft.

Min. 8 inch

Min. 4 ft.

 

 

Min. 1 ft.

 

Min. 1 ft. 2 inch

 

Air

 

 

 

 

discharge

 

 

 

 

 

 

 

 

 

 

chamber

 

 

 

Min. 1 ft. 2 inch

 

 

 

Min. 12 ft.

 

 

 

 

 

 

 

 

 

Min. 1 ft.

 

Min. 8 inch

 

 

 

Min. 1 ft.

If you would like to make the separation smaller on the air

 

Only up to 3 units can be installed side-by-side under the above

 

discharge side, use an air discharge chamber.

 

conditions. The next group must be spaced at least 1 ft. away

You can install any number of units side-by -side.

 

from the first group.

Air in

Air discharge

Concrete block

4 inch × 1 ft. 4 inch beams or equal

Anchor bolts (4 pieces)

0933_C_S

Air in

Min. 6 inch

0934_C_I

Fig. 2-3

SM830082

I - 101

Page 105