4. Service procedures

11)Symptoms: LCD on the remote controller displays “CHECK P03”. (Alarm for unusual discharge temp. of compressor)

Start

Unusual discharge gas temperature

Refrigerant shortage

Clogged refrigerant circuit

Electronic refrigerant control valve defect (indoor unit)

0343_M_I

12)Symptom: LCD on the remote controller displays “CHECK P04”. (High-pressure switch activation warning)

Start

The system does not operate again.

Yes

High-pressure switch activation

(Both cooling and heating)

Electronic refrigerant control valve defect

Refrigerant over-charged (Cooling)

Outdoor unit, heat exchanger dirty, clogged

Outdoor unit air short

Outdoor fan stopped

(Heating)

Outdoor unit air short

Indoor unit, heat exchanger dirty, clogged

Large pipe side service valve closed

Indoor fan stop

Air filter clogged

No

Are there connection defects in the wiring?

No

High-pressure switch defect

Yes

Repair the wiring.

4

0344_M_I