1

1. Specifications

Indoor model: UH3642 / Outdoor model: CH3642

Cooling

 

 

 

Indoor Unit

 

Outdoor Unit

 

Complete Unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan Motor

Fan Motor

 

 

Compressor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Performance at

 

 

230

- 208 V / 1 phase / 60 Hz

 

 

230 - 208 V / 1 phase / 60 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rating conditions

A

 

1

-

1

1.8

- 1.8

 

 

12.3 - 13.7

 

15.1

- 15.7

 

 

 

 

 

 

 

 

 

 

 

 

 

kW

 

0.22 - 0.2

0.36

- 0.34

 

 

2.77 - 2.63

 

3.35

- 3.17

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Full load conditions

A

 

1

-

1

1.8

- 1.8

 

 

15.4 - 16.8

 

18.2

- 19.6

 

 

 

 

 

 

 

 

 

 

 

 

 

kW

 

0.22 - 0.2

0.36

- 0.34

 

 

3.45 - 3.38

 

4.03

- 3.92

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Starting amperes

A

 

2

-

2

2

- 2

 

 

95 - 86

 

98

- 89

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor Unit

 

Outdoor Unit

 

Complete Unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan Motor

Fan Motor

 

 

Compressor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Performance at

 

 

230

- 208 V / 1 phase / 60 Hz

 

 

230 - 208 V / 1 phase / 60 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rating conditions

A

 

0.9

-

0.8

1.8

- 1.8

 

 

15.5 - 17

 

18.2

- 19.6

 

 

 

 

 

 

 

 

 

 

 

 

 

kW

 

0.21

-

0.18

0.36

- 0.34

 

 

3.21 - 3.24

 

3.78

- 3.76

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Full load conditions

A

 

0.9

-

0.8

1.8

- 1.8

 

 

14.7 - 16

 

17.4

- 18.6

 

 

 

 

 

 

 

 

 

 

 

 

 

kW

 

0.21

-

0.18

0.36

- 0.34

 

 

3.32 - 3.29

 

3.89

- 3.81

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Starting amperes

A

 

2

-

2

2

- 2

 

 

95 - 86

 

97.9

- 88.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling:

 

 

 

 

 

 

 

 

 

 

 

 

 

Rating Conditions

: Indoor Air Temperature

80

°F DB / 67 °F WB

 

 

 

 

 

Outdoor Air Temperature

95

°F DB

 

 

Full Load Conditions

: Indoor Air Temperature

80

°F DB / 67 °F WB

 

 

 

 

 

Outdoor Air Temperature 115 °F DB

 

 

Heating:

 

 

 

 

 

 

 

 

 

 

 

 

 

Rating Conditions

: Indoor Air Temperature

70

°F DB / 60 °F WB

 

 

 

 

 

Outdoor Air Temperature

47

°F DB / 43 °F WB

 

 

Full Load Conditions

: Indoor Air Temperature

80

°F DB / — °F WB

 

 

 

 

 

Outdoor Air Temperature

45

°F DB / 35 °F WB

 

 

SM830082

I - 114

Page 118
Image 118
Sanyo KH3642 / CH3642, XH3642 / CH3642, XH4242 / CH4242 Specifications Indoor model UH3642 / Outdoor model CH3642