2. Processes and functions

2-6 Condensing Temperature Control (Cooling)

2

Condensing temperature is controlled by the outdoor heat exchanger coil temperature as sensed by sensor C2.

 

140

 

 

OUTDOOR UNIT

 

 

 

COIL TEMP. C2

 

 

 

(°F)

131

 

 

OUTDOOR FAN

FORCED

 

SPEED

H, M or L

H, M or L

H

ELECTRONIC REF.

 

 

CONTROL VALVE

OPEN

 

 

 

 

1926_THS_I

Fig. 9

Chart Explanations and notes

This chart shows how the outdoor fan speed and the electronic refrigerant control valve react to coil temperature to control condensing temperature.

Sensor C2 is located in the middle of the outdoor unit heat exchange coil.

When C2 rises above 140°F the electronic refrigerant control valve opens at 50 steps/30 seconds, and the outdoor fan speed is forced to change to high (H) until C2 falls below 131°F.

SM830082

II - 8

Page 128
Image 128
Sanyo KH3642 / CH3642, XH3642 / CH3642, XH4242 / CH4242, XH2442 / CH2442 service manual Condensing Temperature Control Cooling