Sanyo XH3642 / CH3642, XH4242 / CH4242 Service procedures Checking procedure for each PC Board

Models: TH4242 / CH4242 XH2442 / CH2442 XH3642 / CH3642 KH2442 / CH2442 UH3642 / CH3642 TH2442 / CH2442 UH2442 / CH2442 TH3642 / CH3642 KH3642 / CH3642 XH4242 / CH4242

1 202
Download 202 pages 41.27 Kb
Page 200
Image 200

4

4. Service procedures

(12) Checking procedure for each PC Board

The indoor and outdoor PCBs have functions to check the signal transmission and reception of the serial circuit and to check the microcomputer operation. (Self-diagnosis function)

Precautions required when checking

1.After turning off the power to the indoor (outdoor) unit, remove the inter-unit control wiring (U1-U2) and create a short-circuit between U1 and U2.

2.Short the CHECK PIN on the PC board of the indoor (outdoor) unit and turn on the power.

3.When checking the Outdoor controller, remove the compressor wiring from the compressor electromagnetic contactor.

4-1. Checking the serial circuit

Indoor controller: A lighted LED indicates normal. A blinking LED indicates abnormal.

Outdoor controller: Blinking LEDs (D11 and D22) indicate normal. If one of the LEDs (D11 and D22) goes off, it indicates abnormal.

4-2. Checking microcomputer operation

When the microcomputer works normally, the relays are switched in sequence as below.

Indoor controller

 

 

 

Output

ON time

 

 

 

 

 

 

 

 

 

 

 

Indoor fan

Very high fan speed (HH)

0.5 seconds

 

 

 

 

 

 

 

 

 

 

 

Indoor fan

High fan speed (H)

0.5 seconds

 

 

 

 

 

 

 

 

 

 

 

Indoor fan

Low fan speed (L)

0.5 seconds

 

 

 

 

 

 

 

 

 

 

 

Indoor fan

Very low fan speed (LL)

0.5 seconds

 

 

 

 

 

 

 

 

 

 

 

Flap motor

 

 

 

 

 

0.5 seconds

 

 

 

 

 

 

 

 

 

 

 

Drain pump

 

 

 

 

 

0.5 seconds

 

 

 

 

 

 

 

 

Operation order

Electric heater

0.5 seconds

 

 

 

 

 

 

 

 

 

 

Operation signal

0.5 seconds

 

 

 

 

 

 

 

 

 

 

 

In a lump

 

 

 

 

 

0.5 seconds

 

 

 

 

 

 

 

 

 

 

Electronic control valve A

0.5 seconds

 

 

 

 

 

 

 

 

 

 

Electronic control valve B

0.5 seconds

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Electronic control valve.A

 

 

 

0.5 seconds

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Electronic control valve

B

 

0.5 seconds

 

 

 

 

 

 

 

 

 

 

Outdoor controller

 

 

 

 

 

 

 

 

 

 

 

 

 

Output

ON time

 

 

 

 

 

 

 

 

 

 

 

Outdoor fan

High fan speed (H)

0.5 seconds

 

 

 

 

 

 

 

 

 

Operation order

 

Outdoor fan

Low fan speed (L)

0.5 seconds

 

 

 

 

 

 

 

 

4-way valve

 

 

 

 

 

0.5 seconds

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor

0.5 seconds

 

 

 

 

 

 

 

 

 

SM830082

IV - 44

Page 200
Image 200
Sanyo XH3642 / CH3642, XH4242 / CH4242, XH2442 / CH2442 Service procedures Checking procedure for each PC Board