Sanyo TH4242 / CH4242 service manual Specifications Refrigerant Flow Diagram Outdoor Unit CH4242

Models: TH4242 / CH4242 XH2442 / CH2442 XH3642 / CH3642 KH2442 / CH2442 UH3642 / CH3642 TH2442 / CH2442 UH2442 / CH2442 TH3642 / CH3642 KH3642 / CH3642 XH4242 / CH4242

1 202
Download 202 pages 41.27 Kb
Page 54
Image 54

1. Specifications

1-5 Refrigerant Flow Diagram

Outdoor Unit: CH4242

Indoor Unit: 42 Type

1

Compressor

 

 

Accumulator

 

 

 

Gas line

 

 

service

 

 

valve

High

HP

 

 

Muffler

pressure

 

switch

 

4-way valve

 

 

 

EC

 

 

Heat exchanger

 

P

 

 

Distributor

 

 

 

Liquid line

 

 

service

 

 

valve

Sub-heat exchanger

 

Cooling Cycle

Heating Cycle

O.D.

3/4"

(19.05mm)

O.D.

3/8"

(9.52mm)

Gas line nipple

EC

Heat exchanger

P

Distributor

Strainer

Electronic ref.control valve

M

Liquid line nipple

Strainer

2181_THS_I

1-6 Operating Range

 

Temperature

Indoor Air Intake

Outdoor Air Intake

 

 

 

 

Cooling

Maximum

95 °F DB, 71 °F WB

115 °F DB

Minimum

67 °F DB, 57 °F WB

0 °F DB

 

 

 

 

 

 

Heating

Maximum

80 °F DB, 67 °F WB

75

°F DB, 65 °F WB

 

 

 

 

Minimum

-DB / -WB

17

°F DB / 15 °F WB

 

SM830082

I - 50

Page 54
Image 54
Sanyo TH4242 / CH4242, XH3642 / CH3642 Specifications Refrigerant Flow Diagram Outdoor Unit CH4242, Operating Range