2. Processes and functions
2-8 Discharge Temperature Control (Cooling and Heating)
2 |
This function prevents the compressor motor from burnout by overheating.
| (42 Type) (24, 36 Type) |
|
|
| |
| 275 | 239 |
|
|
|
| 257 | 221 |
|
|
|
| 239 | 203 |
|
|
|
| 235 | 200 |
|
|
|
DISCHARGE GAS |
|
|
|
| |
TEMP. (°F) | 230 | 194 |
|
|
|
|
|
|
| ||
| 221 | 185 |
|
|
|
| OUTDOOR |
|
|
|
|
| FAN SPEED | H OR M |
| L | H OR M |
|
|
|
|
| |
| COMPRESSOR |
|
| ON | |
|
|
|
|
| |
| ELECTRONIC REF. |
|
|
| |
| CONTROL VALVE | OPEN |
| OPEN | |
| (DISCHARGE TEMP.) |
| |||
|
|
|
|
TRIP IS OPERATED.
1928_THS_I
Fig. 11
Chart Summary and Explanations
❑Discharge temperature is sensed by TH8 (discharge gas sensor).
❑When the temperature rises above 203°F (24, 36 Type) the electronic refrigerant control valve opens at 50 steps/30 seconds until the temperature falls below 200°F (24, 36 Type) .
❑During HEATING operation, when the temperature rises above 221°F (24, 36 Type), the control circuit stops the outdoor fan motor until the temperature falls below 194°F (24, 36 Type). Please note that this control does not function during COOLING operation.
❑For both COOLING and HEATING modes, if the temperature reaches 239°F (24, 36 Type) the operation shuts down and alarm P3 appears on the remote controller.
❑The outdoor fan speed is controlled on discharge temp. at heating mode.