4. Service procedures

Test Run Procedure

Start

 

Multiple remote

Yes

control?

 

No

 

Turn on RCU address SW of sub remote control unit

Recheck the test items before test operation.

Check the indoor and outdoor unit combination (wiring).

Yes

Single type?

 

Multiple indoor

Yes

(One indoor unit and one

No

units for one outdoor

 

remote controller for one

 

 

 

 

units?

 

 

outdoor unit)

 

 

 

 

 

 

 

 

 

No

Turn on power supply for indoor units side

 

 

 

first Then turn on power supply for outdoor

 

 

 

 

unit side.

Group control

Yes

for multiple outdoor

 

units?

 

 

Go next

No

R.C. line

 

 

No

Yes

Finish all

 

R.C. line?

Central control

Yes

for multiple outdoor

 

units?

 

 

 

No

Go next

R.C. line

 

No

Yes

Finish all

 

R.C. line?

or

or

Set the outdoor unit R.C. address. Turn on power supply switch.

Press A. ADD (S1) button (See P87).

Execute auto. address operation with the remote controller.

CN4: Open (*)

Set the outdoor unit R.C. address. Turn on power supply switch.

Press A. ADD (S1) button (See P87).

Execute auto. address operation with the remote controller.

4

Display the combination number.

Set the remote controller to test operation.

No

Check according the self-diagnostics function table,

Is operation possible?

see Sec. 12-8, 9, 10, and if there is a location to correct,

 

 

correct it.

 

 

Yes

Note: Check the indoor side drain water.

Return the remote controller to normal.

NOTE

End

1)One of CN006 of all linked outdoor units shold be short.

2)In case of using system controller, zone registration is required after finishing Test run. Regarding the zone registration, please refer to page 74 and 75.