2-13 Electronic Refrigerant Control Valve

2

This valve allows very precise and smooth control of the amount of refrigerant flow in the system. Since the valve is operated by a step motor, the control circuits can open or close it in very exact amounts, so the degree of heating or cooling can be changed by just a little, or changed very quickly or slowly.

(Completely close …… 0 step) (Full open................ 480 step)

Model

 

Min. open

Max. open

 

 

 

HEAT

 

COOL

 

 

 

24 type

100 step

 

100 step

 

 

 

 

 

 

36 type

90 step

 

90 step

480 step

 

 

 

 

 

42 type

100 step

 

100 step

 

Fuzzy Control

Fuzzy Control is a controlling system to control electronic refrigerant control valve using fuzzy logic. It regulates the functions of heating and cooling, as well as some of the processes inside the unit, by taking account of many different conditions of temperature, fan speed, etc. These control circuits work automatically to send just the right amount of refrigerant through the Electronic Refrigerant Control Valve.

2-14 Compressor Discharge Gas Temperature

(A) Cooling

Indoor temp. (°F)

 

68 – 77

79 – 82

84

– 90

 

 

 

 

 

 

 

Outdoor temp. (°F)

55 or below

 

57 – 61

81 – 95

97

– 109

 

 

 

 

 

 

 

Compressor discharge

104 – 176

 

104 – 194

140 – 212

158 – 221

gas temp. (°F)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(B)Heating (Except During Defrosting)

Indoor temp. (°F)

64 – 70

 

 

72

– 77

 

 

 

79

– 86

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor temp. (°F)

32 or below

34

– 50

32 or below

34

– 50

52

– 70

32 or below

34

– 50

52

– 70

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor discharge

104 – 176

122

– 194

122 – 194

122

– 212

140

– 221

122 – 194

140

– 212

158

– 221

gas temp. (°F)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operate the unit at least 30 minutes to stabilize the discharge temperature.

The above discharge temperature was measured with a 15m tubing length. The temperature may vary with tubing length.

SM830082

II - 16

Page 136
Image 136
Sanyo KH2442 / CH2442, XH3642 / CH3642 Electronic Refrigerant Control Valve, Compressor Discharge Gas Temperature