4. Service procedures

Possible Cause of Malfunction

 

Alarm

 

message

 

 

 

 

 

 

 

Thermistor

Indoor thermistor is either open

Indoor coil temp. (E1 = TH1) cannot be detected.

F1

failure

or damaged.

 

 

Indoor coil temp. (E2 = TH2) cannot be detected.

F2

 

 

 

 

 

 

 

 

 

Indoor coil temp. (E3 = TH3) cannot be detected.

F3

 

 

Indoor room (air-intake) temp. can not be detected.

F10

 

 

 

 

 

Outdoor thermistor is either

Discharge gas temp. (comp. = TH0A) cannot be detected.

F4

 

open or damaged.

Outdoor coil gas temp. (C2 = TH0C) cannot be detected.

F25

 

 

 

 

 

 

 

 

Outdoor coil liquid temp. (C1 = TH0D) cannot be detected.

F7

EEPROM (ICB of PCB) failure

 

F29

 

 

 

 

Fault with

Protective device for comp. is

Comp. motor is overloaded.

H1

comp. and its

activated.

Comp. motor is locked.

H2

circuit

 

 

Current of comp. cannot be detected when it is turned on.

H3

 

 

 

 

Current of comp. is detected when it is not operated.

F27

 

 

Comp. contactor (Mg SW) is chattering.

H18

Possible cause of Malfunction

Alarm

message

 

Model setting of indoor unit is not matching the outdoor unit.

L2

When using group control, main indoor unit address setting is duplicated.

L3

(Judging by indoor unit.)

 

 

 

Outdoor unit address (R.C. No.) is duplicated.

L4

 

 

Priority setting of indoor unit is duplicated.

L5

 

 

L6

Improper wiring between indoor units.

L7

(There is group connection wiring in case of individual control.)

 

 

 

Capacity code of indoor unit is not set.

L9

Improper wiring of group control wiring.

L11

 

 

Possible Cause of Malfunction (The following messages are displayed only for the system controller.)

Alarm

message

 

 

 

 

 

 

 

• Serial

System controller is transmitting

• Indoor or outdoor unit is not working correctly.

 

commu-

• Control lines between indoor unit, outdoor unit, and system

C05

nication

incorrect signal.

controller are not wired correctly.

 

 

 

errors

 

 

 

System controller is detecting

• Same as for C05, above.

C06

Mis-setting

incorrect signal.

• Connector CN1 is not connected correctly.

 

 

 

 

 

Activation of

Protective device of the sub-

When using wireless remote controller or system controller,

P30

protective

indoor unit is activated in group

connect wired remote controller with the indoor unit temporarily

device

contorl.

to check the alarm message in detail.

 

 

 

 

 

NOTE

R.C. : Refrigerant Circuit

comp. : Compressor

temp. : Temperature

PCB : Printed Circuit Board

SM830082

4

IV - 7

Page 163
Image 163
Sanyo UH3642 / CH3642, XH3642 / CH3642, XH4242 / CH4242, XH2442 / CH2442 Possible cause of Malfunction Alarm Message