1. Specifications

1-1 Unit Specifications

 

MODEL No.

Indoor Unit

 

 

 

 

XH3642

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor Unit

 

 

 

 

CH3642

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

POWER SOURCE

 

 

 

 

230 - 208 V / 1 Phase / 60 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PERFORMANCE

 

 

 

Cooling

 

 

Heating

 

 

 

 

 

 

 

 

 

 

 

 

 

Capacity*

(17°F)**

BTU / h

34,500

 

33,500

 

37,500

 

36,500

 

 

 

 

 

 

 

 

25,000

 

23,500

 

Moisture removal (High)

 

Pints / h

10.5

 

10.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air circulation (H / M / L)

230 V

cu.ft. / min.

 

 

1,050 / 840 / 720

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S.E.E.R. (H.S.P.F.)

 

BTU / Wh

10.7

 

11.0

 

(7.0)

 

 

(7.0)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ELECTRICAL RATINGS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage rating

 

 

VAC

230

 

208

 

230

 

208

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Available voltage range

 

 

VAC

 

 

 

187 - 253

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Running amperes

 

 

A

15.4

 

15.8

 

18.2

 

 

19.3

 

 

 

 

 

 

 

 

 

 

 

 

 

Power input*

 

 

W

3,350

 

3,200

 

3,850

 

 

3,750

 

 

(17°F)**

 

 

 

 

 

 

3,150

 

2,950

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum overcurrent protection

 

 

A

 

 

 

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FEATURES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Controls

 

 

 

 

 

Microprocessor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low ambient control

 

 

 

 

 

 

Built-in 0°F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan speeds Indoor / Outdoor

 

 

 

 

3 and Automatic control / 3 (Auto)

 

 

 

 

 

 

 

 

 

 

 

 

Optional Wired Remote Controller (Timer)

 

 

 

RCS-SH80UG (72-hour ON / OFF)

 

 

 

 

 

 

 

 

Optional Wireless Remote Controller (Timer)

 

 

RCS-SH80UA. WL / RCS-BH80UA. WL (72-hour ON / OFF)

 

 

 

 

 

 

 

 

 

 

 

 

Air deflection

Horizontal / Vertical

 

 

— / Automatic

 

 

 

 

 

 

 

 

 

 

 

Air filter

 

 

 

Washable, easy access, long life fiter (2,500 hr)

 

 

 

 

 

 

 

 

 

 

 

 

 

Operation sound

Indoor - Hi / Me / Lo

 

dB - A

 

 

44 / 37 / 33

 

 

 

 

 

Outdoor - Hi

 

dB - A

 

 

 

56

 

 

 

 

 

 

 

 

 

 

 

 

 

Refrigerant control

 

 

 

 

Electronic Expansion Control Valve

 

 

 

 

 

 

 

 

 

 

 

 

 

 

REFRIGERANT PIPING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Limit of piping length

 

ft.

(m)

 

 

 

165 (50)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Limit of piping length at shipment

 

ft.

(m)

 

 

 

100 (30)

 

 

 

 

 

 

 

 

 

 

 

Limit of elevation difference

 

ft.

(m)

Outdoor unit is higher than indoor unit: 165 (50)

 

between the two units

 

 

 

Outdoor unit is lower than indoor unit: 100 (30)

 

 

 

 

 

 

 

 

 

 

 

 

 

Refrigerant piping

Narrow pipe

in. (mm)

 

 

 

3 / 8 (9.52)

 

 

 

 

Flare type

Wide pipe

in. (mm)

 

 

3 / 4 (19.05)

 

 

 

 

DIMENSIONS & WEIGHT

 

 

 

Indoor unit

 

Outdoor unit

 

 

 

 

 

 

 

 

 

 

 

Unit dimensions

Height

in. (mm)

14-1/2

 

(368)

 

48-5/8

(1,235)

 

 

 

 

 

 

 

 

 

 

 

 

Width

in. (mm)

41-31/32

 

(1,066)

 

37-1/32

(940)

 

 

 

 

 

 

 

 

 

 

 

 

Depth

in. (mm)

30-9/16

 

(776)

 

13-3/8

(340)

 

 

 

 

 

 

 

 

 

 

 

Net weight

 

lbs. (kg)

60

 

(27)

 

203

(92)

 

 

 

 

 

 

 

 

 

 

 

Indoor grille dimensions

Height

in. (mm)

3-1/16

 

(78)

 

 

 

 

 

 

 

 

 

 

 

 

 

PNR-XHS2432

Width

in. (mm)

45-9/32

 

(1,150)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Depth

in. (mm)

33-27/32

 

(860)

 

 

 

 

 

 

 

 

 

 

 

 

 

Net weight

 

lbs. (kg)

15

 

(7)

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor / Outdoor unit

Height

in. (mm)

14-1/2

 

(368)

 

52-7/32

(1,326)

 

 

 

 

 

 

 

 

 

 

 

Package dimensions

Width

in. (mm)

44-9/32

 

(1,125)

 

40

(1,016)

 

 

 

 

 

 

 

 

 

 

 

 

Depth

in. (mm)

33-9/32

 

(845)

 

16-3/8

(416)

 

 

 

 

 

 

 

 

 

 

 

Shipping weight

 

lbs. (kg)

71

 

(32)

 

227

(103)

 

 

 

 

 

 

 

 

 

 

 

Shipping volume

 

cu.ft. (m3)

12.4

 

(0.35)

 

19.8

(0.56)

 

Indoor grille

Height

in. (mm)

4-3/32

 

(104)

 

 

 

 

 

 

 

 

 

 

 

 

 

Package dimensions

Width

in. (mm)

49-1/2

 

(1,257)

 

 

 

 

 

 

 

 

 

 

 

 

 

PNR-XHS2432

Depth

in. (mm)

39-11/32

 

(999)

 

 

 

 

 

 

 

 

 

 

 

 

 

Shipping weight

 

lbs. (kg)

22

 

(10)

 

 

 

 

 

 

 

 

 

 

 

 

 

Shipping volume

 

cu.ft. (m3)

4.6

 

(0.131)

 

 

DATA SUBJECT TO CHANGE WITHOUT NOTICE

Cooling :

Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB Heating :

Rating conditions (*) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 47 °F DB / 43 °F WB

Low temp conditions (**) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 17 °F DB / 15 °F WB

SM830082

1

I - 3

Page 7
Image 7