DVP - ES2/EX2/SS2/SA2/SX2/SE Operation Manual - Programming

Error code

Description

Action

 

 

 

C40B

MC / MCR does not begin from N0 or discontinuously

A circuit error occurs

C40C

MC / MCR corresponding value N is different

if a combination of

 

 

instructions is

C40D

Use I / P incorrectly

incorrectly specified.

 

 

C40E

IRET doesn’t follow by the last FEND instruction

 

SRET doesn’t follow by the last FEND instruction

Select programming

 

 

PLC program and data in parameters have not been

mode and correct the

C40F

identified error

initialized

 

 

 

 

 

C41B

Invalid RUN/STOP instruction to extension module

 

 

 

 

C41C

The number of input/output points of I/O extension unit is

 

larger than the specified limit

 

 

 

 

 

 

C41D

Number of extension modules exceeds the range

 

C41F

Failing to write data into memory

 

C430

Initializing parallel interface error

 

C440

Hardware error in high-speed counter

 

C441

Hardware error in high-speed comparator

 

C442

Hardware error in MCU pulse output

 

C443

No response from extension unit

 

C4EE

No END command in the program

 

 

 

 

C4FF

Invalid instruction (no such instruction existing)

 

 

 

 

6.3Error Detection Devices

Error Check

Description

Drop Latch

 

STOP Æ RUN

RUN Æ STOP

Devices

 

 

 

 

 

 

 

 

 

 

 

 

M1067

Program execution error flag

None

 

Reset

Latch

 

 

 

 

 

 

M1068

Execution error latch flag

None

 

Latch

Latch

 

 

 

 

 

 

D1067

Algorithm error code

None

 

Reset

Latch

 

 

 

 

 

 

D1068

Step value of algorithm errors

None

 

Latch

Latch

 

 

 

 

 

 

 

 

 

 

 

 

Device D1067

 

Description

 

 

Error Code

 

 

 

 

 

 

 

 

0E18

BCD conversion error

 

 

 

 

 

 

 

 

 

 

0E19

Division error (divisor=0)

 

 

 

 

 

 

 

 

0E1A

Floating point exceeds the usage range

 

 

 

 

 

 

0E1B

The value of square root is negative

 

 

 

 

 

 

 

 

6 - 6