DVP - ES2/EX2/SS2/SA2/SX2/SE Operation Manual - Programming

Feedback

 

Explanation

Data storage

 

 

 

D1076 low

N

format.

 

A

Retrieved status content. The content of ”ABCD” differs

D1077 low

B

according to value 00~03 set in NN. 00 ~ 03 indicates

D1078 low

C

frequency, current and operation mode respectively.

D1079 low

D

Please refer to the explanations below for details.

D1080 low

 

Nn = “00”

Frequency command = ABC.D (Hz)

 

 

Nn = “01”

Output frequency = ABC.D (Hz)

 

 

Nn = “02”

Output current = ABC.D (A)

 

PLC will automatically convert the ASCII characters ”ABCD” into D1050. For example, ”ABCD” = “0600”, PLC will convert ABCD into K0600 (0258 H) and store it in the special register D1050.

Nn = “03”

 

 

Operation command

 

 

 

 

 

 

‘A’ =

 

‘0’

 

Stop,

 

 

 

‘5’

 

JOG (forward)

 

 

 

 

‘1’

 

Forward operation

 

‘6’

 

JOG (reverse)

 

 

 

 

‘2’

 

Stop,

 

 

 

‘7’

 

JOG (reverse)

 

 

 

 

‘3’

 

Reverse operation

 

‘8’

 

Abnormal

 

 

 

 

‘4’

 

JOG (forward),

 

 

 

 

 

 

 

 

PLC will automatically convert the ASCII character in ”A” into D1051.

 

 

For example, ”A” = “3”, PLC will convert A into K3 and store it in the

 

 

special register D1051.

 

 

 

 

 

 

 

 

‘B’ =

b7

 

b6

 

b5

 

b4

 

Frequency reference source

 

 

 

0

 

0

 

0

 

 

0

 

 

 

 

Digital keypad

 

 

 

0

0

 

0

 

 

1

 

 

 

 

1st Step Speed

 

 

 

0

0

 

1

 

 

0

 

 

 

 

2nd Step Speed

 

 

 

0

0

 

1

 

 

1

 

 

 

 

3rd Step Speed

 

 

 

0

1

 

0

 

 

0

 

 

 

 

4th Step Speed

 

 

 

0

1

 

0

 

 

1

 

 

 

 

5th Step Speed

 

 

 

0

1

 

1

 

 

0

 

 

 

 

6th Step Speed

 

 

 

0

1

 

1

 

 

1

 

 

 

 

7th Step Speed

 

 

 

1

0

 

0

 

 

0

 

 

 

 

JOG frequency

 

 

 

1

0

 

0

 

 

1

 

Analog input frequency command

 

 

1

0

 

1

 

 

0

 

RS-485 communication interface

 

 

1

0

 

1

 

 

1

 

 

 

Up/Down control

 

 

 

b3

= 0

 

Non-DC braking stop

1

 

DC braking stop

 

 

 

b2

=

0

Non-DC braking start

1

 

DC braking start

 

 

 

b1

=

0

Forward

 

 

 

1

 

Reverse

 

 

 

b0

=

0

Stop

 

 

 

1

 

Run

 

 

 

PLC will store bit status of ”B” in special auxiliary relay M1168 (b0) ~

 

 

M1175 (b7).

 

 

 

 

 

 

 

 

 

 

 

 

“CD” =

 

 

“00”

 

 

 

 

No error

 

 

“10”

 

OcA

 

 

 

 

“01”

 

 

 

 

 

oc

 

 

 

“11”

 

Ocd

 

 

 

 

“02”

 

 

 

 

 

ov

 

 

 

“12”

 

Ocn

 

 

 

 

“03”

 

 

 

 

 

oH

 

 

 

“13”

 

GFF

 

 

 

 

“04”

 

 

 

 

 

oL

 

 

 

“14”

 

Lv

 

 

 

 

“05”

 

 

 

 

 

oL1

 

 

 

“15”

 

Lv1

 

 

 

 

“06”

 

 

 

 

 

EF

 

 

 

“16”

 

cF2

 

 

 

 

“07”

 

 

 

 

 

cF1

 

 

 

“17”

 

bb

 

 

 

 

“08”

 

 

 

 

 

cF3

 

 

 

“18”

 

oL2

 

 

 

 

“09”

 

 

 

 

 

HPF

 

 

“19”

 

 

PLC will automatically convert the ASCII characters in ”CD” into D1052. For example, ”CD” = “16”, PLC will convert CD into K16 and store it in the special register D10512

8.M1177 = ON, other Delta VFDs are supoported

3 - 284