DVP - ES2/EX2/SS2/SA2/SX2/SE Operation Manual - Programming

M1002

 

 

Set up communication protocol as

 

 

 

 

MOV

H86

D1120

 

 

 

 

9600, 7, E, 1

 

 

 

 

 

 

 

 

 

 

 

SET

M1120

Retain communication protocol

 

 

 

 

 

 

 

 

MOV

K100

D1129

Set up communication time-out: 100ms

 

 

 

 

 

X0

 

 

 

M1129

X0

SET M1122 Sending request

RSTEF

K1

K0

Communication instruction setting:

Device address: 1 K0: Reserved

 

 

 

Receiving completed

M1127

Processing received data

 

 

 

 

 

 

 

RST M1127 Reset M1127.

 

 

 

 

 

 

PLC

VFD, PLC sends: “:01 06 2002 0002 D5

VFD

PLC, PLC sends: “:01 06 2002 0002 D5

Data to be sent (sending messages):

 

 

 

 

 

 

 

 

 

 

 

 

 

Data

 

 

Descriptions

 

 

‘0’

 

30 H

 

ADR 1

AC drive address : ADR (1,0)

 

 

 

 

 

 

 

 

 

 

‘1’

 

31 H

 

ADR 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

‘0’

 

30 H

 

CMD 1

Command code: CMD (1,0)

 

 

 

 

 

 

 

 

 

 

‘6’

 

36 H

 

CMD 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

‘2’

 

32 H

 

 

 

 

 

 

 

 

 

 

 

 

 

‘0’

 

30 H

 

Data address

 

 

 

 

 

 

 

 

 

‘0’

 

30 H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

‘2’

 

32 H

 

 

 

 

 

 

 

 

 

 

 

 

 

‘0’

 

30 H

 

 

 

 

 

 

 

 

 

 

 

 

 

‘0’

 

30 H

 

Data contents

 

 

 

 

 

 

 

 

 

‘0’

 

30 H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

‘2’

 

32 H

 

 

 

 

 

 

 

 

 

 

 

 

‘D’

 

44 H

LRC CHK 1

Error checksum: LRC CHK (0,1)

 

 

 

 

 

 

 

 

 

 

‘5’

 

35 H

LRC CHK 0

 

 

 

 

 

 

 

 

 

 

 

 

 

3 - 288

Page 404
Image 404
Delta DVP-ES2/EX2/SS2/SA2/SX2/SE manual Rstef