7 CANopen Function and Operation

PDO transmission type can be synchronous transmission and asynchronous transmission. In synchronous transmission, master will send out the SYNC message in the fixed cycle. The length of the cycle is set in master properties dialog box with the default value: 50ms. In asynchronous transmission, the message is sent out once the PDO mapping parameter is changed.

PDO Transmission types in details are introduced in the following table.

 

Transmission Type

 

Description

 

Remark

 

 

 

 

 

 

 

 

 

 

 

Once any change for the mapped data

 

 

 

 

 

 

happens, RxPDO data are sent out

 

 

 

 

RxPDO

 

immediately. The data that slave receives

 

 

 

 

 

are valid only when receiving the next

 

 

 

 

 

 

 

 

 

 

 

 

SYNCH message. If no change for RxPDO

 

SYNCH

 

 

 

 

data, they are not sent out.

 

0

 

 

 

SYNCH

 

 

 

 

 

 

 

 

non-cycle

 

Once any change for the mapped data

 

 

 

 

 

 

 

 

 

 

 

 

 

happens and slave receives the SYNC

 

 

 

 

TxPDO

message, the data are sent out immediately.

 

 

 

 

The TxPDO data are valid immediately after

 

 

 

 

 

 

 

 

 

 

master receives them. If no change for

 

 

 

 

 

TxPDO data, the data are not sent out.

 

 

 

 

 

 

 

 

 

 

 

 

 

After N messages are sent out and no

 

 

 

 

RxPDO

 

matter whether the mapped data are

 

 

 

 

 

changed, the data that slave receives will be

 

 

 

 

 

 

valid only when receiving the next SYNCH

 

SYNCH

 

N

 

 

message.

 

 

N:1~240

 

 

 

 

cycle

 

 

After N messages are sent out and no

 

 

 

 

 

 

 

 

 

TxPDO

matter whether the mapped data are

 

 

 

 

changed, the data that master receives will

 

 

 

 

 

 

 

 

 

 

be valid at once.

 

 

 

 

 

 

 

 

 

 

 

 

 

The mapped data are sent out immediately

 

 

 

 

RxPDO

 

once changed and they are valid once they

 

 

 

 

 

are received by slave. RxPDO data will not

 

 

 

 

 

 

 

 

 

 

 

 

be sent out if no change for the data.

 

 

 

 

 

 

 

 

254

 

Slave sends out the data once every one

 

ASYNCH

 

Event timer time and after that, the TxPDO

 

 

 

 

data are not allowed to be sent out within an

 

 

 

 

TxPDO

inhibit timer time.

 

 

 

 

When Event timer and Inhibit timer are both

 

 

 

 

 

 

 

 

 

 

equal to 0, TxPDO data are sent to master

 

 

 

 

 

immediately once changed and the data

 

 

 

 

 

that master receives will be valid at once.

 

 

 

 

 

 

 

 

255

 

 

Same as Type254

 

 

 

 

 

 

 

 

 

Note:

1> Synchronous transmission type can fulfill multi-axis motion at the same time.

2> If user is going to monitor the real-time changing parameter such as the actual rotation speed of the motor, we suggest TxPDO should be set as the synchronous transmission type in case the frequent changing of slave data causes to block the CANopen network.