DVP - ES2EX2/SS2/SA2/SX2/SE Operation Manual - Programming

5.6IST Instruction

API

Mnemonic

Operands

Function

Controllers

60

IST

 

Initial State

ES2/EX2 SS2 SA2 SX2

Type

Bit Devices

 

Word devices

 

 

 

Program Steps

OP

X

Y

M

S

K

H KnX KnY KnM KnS T

C D

E

F

IST: 7 steps

S

*

*

*

 

 

 

 

 

 

 

D1

 

 

 

*

 

 

 

 

 

 

D2

 

 

 

*

 

 

 

 

 

 

 

 

 

 

 

 

PULSE

 

16-bit

 

32-bit

 

 

 

 

 

 

ES2/EX2 SS2 SA2 SX2 ES2/EX2 SS2 SA2 SX2 ES2/EX2 SS2 SA2 SX2

Operands:

S: Source device for assigning pre-defined operation modes (8 consecutive devices). D1 The

smallest No. of step points in auto mode. D2: The greatest No. of step points in auto mode.

Explanations:

1.The IST is a handy instruction specifically for the initial state of the step ladder operation modes.

2.The range of D1 and D2 : S20~S911, D1 < D2.

3.IST instruction can only be used one time in a program.

Program Example 1:

M1000

 

 

 

IST

X20

S20

S60

S:

X20: Individual operation (Manual operation)

X24: Continuous operation

 

X21: Zero return

X25: Zero return start switch

 

X22: Step operation

X26: Start switch

 

X23: One cycle operation

X27: Stop switch

1.When IST instruction is executed, the following special auxiliary relays will be assigned automatically.

M1040: Movement inhibited

S0: Manual operation/initial state step point

M1041: Movement start

S1: Zero point return/initial state step point

M1042: Status pulse

S2: Auto operation/initial state step point

M1047: STL monitor enable

 

2.When IST instruction is used, S10~S19 are occupied for zero point return operation and cannot be used as a general step point. In addition, when S0~S9 are in use, S0 initiates

5 - 22

Page 644