3. Instruction Set

 

 

 

 

 

 

 

 

 

Flag

Function

Action

 

M1121

Data transmission ready. M1121 = OFF indicates that RS-485 in

System

 

COM2 is transmitting

 

sets

 

 

 

 

 

 

 

 

Sending request. Before executing communication instructions,

 

 

 

users need to set M1122 to ON by trigger pulse, so that the data

User sets,

 

M1122

sending and receiving will be started. When the communication is

system

 

 

resets

 

 

completed, PLC will reset M1122 automatically.

 

 

 

 

 

 

 

 

 

Data receiving completed. When data receiving of communication

 

 

 

instructions is completed, M1123 will be ON. Users can process the

System

 

M1123

received data when M1123 is ON. When data processing is

sets ON

 

and user

 

 

completed, M1123 has to be reset by users.

 

 

resets

 

 

Supported communication instructions: RS

 

 

 

 

 

 

M1124

Data receiving ready. When M1124 is ON, PLC is ready for data

System

 

receiving..

sets

 

 

 

 

 

 

 

 

 

 

 

Communication ready status reset. When M1125 is set ON, PLC

 

 

M1125

resets the communication (transmitting/receiving) ready status.

 

 

M1125 has to be reset by users after resetting the communication

 

 

 

 

 

 

ready status.

 

 

 

 

 

 

 

Set STX/ETX as user-defined or system-defined in RS

User

 

 

 

 

M1126

communication. For details please refer to the table in point 5.

sets/resets

 

 

M1126 only supports RS instruction.

 

 

 

 

 

 

 

Set STX/ETX as user-defined or system-defined in RS

 

 

M1130

communication. For details please refer to the table in point 5.

 

 

 

M1130 only supports RS instruction

 

 

 

 

 

 

 

COM2 (RS-485) data sending/receiving/converting completed. RS

 

 

 

instruction is NOT supported.

System

 

 

 

 

M1127

Supported communication instructions:

sets and

 

 

MODRD / MODWR / FWD / REV / STOP / RDST / RSTEF /

user resets

 

 

 

 

 

MODRW

 

 

 

 

 

 

M1128

Transmitting/receiving status indication.

System

 

sets

 

 

 

 

 

Receiving time out. If users set up time-out value in D1129 and the

System

 

 

 

 

M1129

data receiving time exceeds the time-out value, M1129 will be set

sets and

 

 

ON.

user resets

 

 

 

 

 

 

 