3. Instruction Set

 

Register

Data

Descriptions

 

D1260 Low

00 H

Number of Data (count by word)

 

 

 

 

D1261 Low

10 H

 

 

 

 

 

 

 

D1262 Low

79 H

CRC CHK Low

 

 

 

 

 

D1263 Low

0A H

CRC CHK High

 

 

 

 

Registers for received data (responding messages)

 

Register

 

Data

 

 

 

Descriptions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D0

 

 

1234 H

PLC stores the value 1234H into D1296

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D1 Low

 

 

02 H

Function

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D2 Low

 

 

02 H

Number of Data (Byte)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D3 Low

 

 

34 H

Content of address

 

 

 

 

 

 

D4 Low

 

 

12 H

H0500~H0515

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D5 Low

 

 

2F H

CRC CHK Low

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D6 Low

 

 

75 H

CRC CHK High

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Analysis of the read status of PLC2 Y0~Y17: 1234H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Device

Status

Device

 

Status

Device

 

 

Status

Device

Status

 

Y0

OFF

Y1

 

OFF

Y2

 

 

ON

Y3

OFF

 

Y4

ON

Y5

 

ON

Y6

 

 

OFF

Y7

OFF

 

Y10

OFF

Y11

 

ON

Y12

 

 

OFF

Y13

OFF

 

Y14

ON

Y15

 

OFF

Y16

 

 

OFF

Y17

OFF

Program Example 2: COM1(RS-232) / COM3(RS-485), Function Code H02

1.Function code K2 (H02): read multiple bit devices. Up to 64 bits can be read.

2.PLC1 connects to PLC2: (M1320 = OFF, ASCII mode), (M1320 = ON, RTU mode)

3.For both ASCII and RTU modes, PLC COM1/COM3 only stores the received data in registers starting from S, and will not store the data to be sent. The stored data can be transformed and moved by using DTM instruction for applications of other purposes.

4.Take the connection between PLC1 (PLC COM3) and PLC2(PLC COM1) for example, the tables below explains the status when PLC1 reads Y0~Y17 of PLC2

z If PLC1 applies COM1 for communication, the below program can be usable by changing:

1.D1109→D1036: communication protocol

2.M1136→M1138: retain communication setting

3.D1252→D1249: Set value for data receiving timeout

4.M1320→M1139: ASCII/RTU mode selection

5.M1316→M1312: sending request

6.M1318→M1314: receiving completed flag