3. Instruction Set

46.When M1113 = ON, the unit of Y2 output pulse is 10μs, when M1113 = OFF, the unit is 100μs. (It is not applicable to DVP-SE.)

47.When M1113 = ON, the unit of Y2 output pulse is 100μs, when M1113 = OFF, the unit is 1ms. (It is only applicable to DVP-SE.)

48.When M1071 = ON, the unit of Y3 output pulse is 100μs, when M1071 = OFF, the unit is 1ms.

49.When M1116 is ON, M1112 and M1113 do not work. The time unit of the pulse output through Y0 and Y2 is 1μs. DVP-ES2 version 3.00/SS2 version 2.80/SA2 version 2.60/SE version 2.60/SX2 version 2.40 support this function.

50.When M1117 is ON, M1070 and M1071 do not work. The time unit of the pulse output through Y1 and Y3 is 10μs. DVP-ES2 version 3.00/SS2 version 2.80/SA2 version 2.60/SE version 2.60/SX2 version 2.40 support this function.

51.If M1116 for DVP-SS2 is enabled, the minimum pulse output width should be larger than 20. Otherwise, due to the limitations on the hardware bandwidth of Y0 and Y2, the output result is not the correct time width.

Program Example:

When X0 = ON, Y1 output the pulse as shown opposite. When X0 = OFF, output Y1 turns OFF.

X0 PWM K1000 K2000 Y1

t=1000ms

Output Y1

T=2000ms

Note:

1. Flag description:

M1070: Switching clock pulse of Y1 for PWM instruction (ON:100 us, OFF: 1ms)

M1071: Switching clock pulse of Y3 for PWM instruction (ON:100 us, OFF: 1ms)

M1112 Switching clock pulse of Y0 for PWM instruction (ON:10 us/100µs for SE; OFF: 100 us/1ms for SE)

M1113 Switching clock pulse of Y2 for PWM instruction (ON:10 us, OFF: 100 us) M1116 If M1116 is ON, the time unit of the pulse output through Y0 and Y2 is 1μs.

M1112 and M1113 do not work.

M1117 If M1117 is ON, the time unit of the pulse output through Y1 and Y3 is 10μs. M1070 and M1071 do not work.

2. Special D registers description:

D1030 PV of Y0 pulse output (Low word)

D1031 PV of Y0 pulse output (High word)

3 - 1 4 3

Page 259
Image 259
Delta DVP-ES2/EX2/SS2/SA2/SX2/SE manual =1000ms Output Y1 =2000ms