2. Programming Concepts

Function Group ID of right side modules on ES2/EX2

Number

D1320~ D1327

Contents:

When right side modules are connected on ES2/EX2, the ID of each I/O module will be stored in D1320~D1327 in connection order.

ID of each special module:

Name

ID (HEX)

DVP04AD-E2

H’0080

 

 

DVP02DA-E2

H’0041

 

 

DVP04DA-E2

H’0081

 

 

Name

ID (HEX)

DVP06XA-E2

H’00C4

 

 

DVP04PT-E2

H’0082

 

 

DVP04TC-E2

H’0083

 

 

Function Group ID of left side modules on SA2/SX2

Number D1386~D1393

Contents:

When left side modules are connected on SA2/SX2, the ID of each I/O module will be stored in D1386~D1393 in connection order.

ID of each special module:

Name

ID (HEX)

 

Name

ID (HEX)

DVP04AD-SL

H’4480

 

DVP01HC-SL

H’4120

 

 

 

 

 

DVP04DA-SL

H’4441

 

DVP02HC-SL

H’4220

 

 

 

 

 

DVP04PT-SL

H’4402

 

DVPDNET-SL

H’4131

 

 

 

 

 

DVP04TC-SL

H’4403

 

DVPEN01-SL

H’4050

 

 

 

 

 

DVP06XA-SL

H’6404

 

DVPMDM-SL

H’4040

 

 

 

 

 

DVP01PU-SL

H’4110

 

DVPCOPM-SL

H’4133

 

 

 

 

 

Function Group Output clear signals when ZRN is completed

Number M1346

Contents:

When M1346 = ON, PLC will output clear signals when ZRN is completed. The clear signals to Y0, Y1 will be sent by Y4 for 20ms, and the clear signals to Y2, Y3 will be sent by Y5 for 20ms.

Function Group PLC LINK

Number

M1350-M1356, M1360-M1439, D1355-D1370, D1399, D1415-D1465, D1480-

D1991

 

Contents:

 

1.PLC LINK supports COM2 (RS-485) with communication of up to 16 slaves and access of up to 50 words.

2.Special D and special M corresponding to Slave ID1~ Slave ID8: (M1353 = OFF, access available for only 16 words)

2 - 7 3

Page 105
Image 105
Delta DVP-ES2/EX2/SS2/SA2/SX2/SE manual Number D1320~ D1327 Contents, Number M1346 Contents, Function Group PLC Link Number