2. Programming Concepts

Special

Content

ES2

SS

SA

SX

OFF

STOP

RUN

Attrib.

Latch

Default

D

EX2

2

2

2

Ø

Ø

Ø

-ed

ON

RUN

STOP

 

 

 

 

 

 

 

 

 

 

 

 

Feedback data (ASCII) of Modbus

 

 

 

 

 

 

 

 

 

 

D1070

communication. When PLC’s RS-485

 

 

 

 

 

 

 

 

 

 

communication instruction receives feedback

0

-

-

R

NO

0

signals, the data will be saved in the registers

D1085

 

 

 

 

 

 

 

 

 

 

 

D1070~D1085. Usres can check the received

 

 

 

 

 

 

 

 

 

 

 

data in these registers.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D1086

High word of the password in DVP-PCC01

0

-

-

R/W

NO

0

(displayed in hex according to its ASCII codes)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D1087

Low word of the password in DVP-PCC01

0

-

-

R/W

NO

0

(displayed in hex according to its ASCII codes)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sent data of Modbus communication.

 

 

 

 

 

 

 

 

 

 

D1089

When PLC’s RS-485 communication instruction

0

-

-

R

NO

0

sends out data, the data will be stored in

D1099

D1089~D1099. Users can check the sent data in

 

 

 

 

 

 

 

 

 

 

 

these registers.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D1109*

COM3 (RS-485) Communication protocol

H’86

-

-

R/W

NO

H’86

 

 

 

 

 

 

 

 

 

 

 

 

D1110*

Average value of EX2/SX2 analog input channel 0

 

 

 

 

0

-

-

R

NO

0

(AD 0) When average times in D1062 is set to 1,

 

D1110 indicates present value.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D1111*

Average value of EX2/SX2 analog input channel 1

 

 

 

 

0

-

-

R

NO

0

(AD 1) When average times in D1062 is set to 1,

 

D1111 indicates present value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D1112*

Average value of EX2/SX2 analog input channel 2

 

 

 

 

0

-

-

R

NO

0

(AD 2) Whenaverage times in D1062 is set to 1,

 

D1112 indicates present value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Average value of 20EX2/SX2 analog input

 

 

 

 

0

-

-

R

NO

0

 

channel 3 (AD 3) Whenaverage times in D1062 is

D1113*

set to 1, D1113 indicates present value

 

 

 

 

 

 

 

 

 

 

 

Displaying the status of the analog input channel

0

-

-

R

NO

0

 

of 30EX2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Enable/disable 20EX2/SX2 AD channels

 

 

 

 

 

 

 

 

 

 

D1114*

(0: enable (default) / 1: disable)

0

-

-

R/W

YES

0

bit0~bit3 sets AD0~AD3.

 

 

 

 

 

 

 

 

 

P.S. 30EX2 does not support this function.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D1115*

20EX2/SX2 analog input/output mode setting

0

0

0

R/W

YES

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30EX2 analog input/output mode setting

-

-

-

R/W

YES

H’FFFF

 

 

 

 

 

 

 

 

 

 

 

 

D1116*

Output value of analog output channel 0 (DA 0) of

0

0

0

R/W

NO

0

EX2/SX2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output value of analog output channel 1 (DA 0) of

 

 

 

 

 

 

 

 

 

 

D1117*

20EX2/SX2

0

0

0

R/W

NO

0

 

P.S. 30EX2 does not support this function.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D1118*

EX2/SX2 sampling time of analog/digital

 

 

 

 

2

-

-

R/W

YES

2

converstion. Default: 2. Unit: 1ms. Sampling time

 

will be regarded as 2ms if D11182

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D1120*

COM2 (RS-485) communication protocol

H’86

-

-

R/W

NO

H’86

 

 

 

 

 

 

 

 

 

 

 

 

D1121*

COM1(RS-232) and COM2(RS-485) PLC

-

-

-

R/W

Yes

1

communication address

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D1122

COM2(RS-485) Residual number of words of

0

0

-

R

NO

0

transmitting data

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D1123

COM2(RS-485) Residual number of words of the

0

0

-

R

NO

0

receiving data

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 - 4 1

Page 73
Image 73
Delta DVP-ES2/EX2/SS2/SA2/SX2/SE manual Yes ’Ffff