DVP - ES2/EX2/SS2/SA2/SX2/SE Operation Manual - Programming

¾If DCNT instruction enables C243 as high speed counter (group A) and DHSC/DHSC instruction uses C245 as high speed counter (group A) at the same time, PLC takes C243 as the source counter automatically and no syntax check error will be detected.

¾Table of settings for the high-speed interrupts of hardware counters and comparators: (It is not applicable to DVP-SE.)

Hardware counter

 

 

A group

 

 

 

B group

 

A1

 

A2

A3

 

A4

B1

 

B2

B3

 

B4

 

 

 

 

 

Counter No.

C243, C245~C248, C251,C252

C244, C249, C250, C253, C254

High-speed counter

I010

 

I020

I030

 

I040

I050

 

I060

I070

 

I080

interrupt

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High-speed compare

 

Share 4 hardware

 

 

Share 4 hardware

 

Set/Reset

comparators for group A

comparators for group B

¾Table of settings for the high-speed interrupts of hardware counters and comparators: (It is only applicable to DVP-SE.)

Hardware counter

 

A group

 

B group

A1

 

A2

B1

 

B2

 

 

 

 

 

 

 

 

 

Counter No.

C243, C245~C248, C251,C252

 

C244

High-speed counter

I010

 

I020

I050

 

I060

interrupt

 

 

 

 

 

 

 

 

Hi-speed compare

Share 2 hardware

Share 2 hardware

Set/Reset

comparators for group A

comparators for group B

¾Block diagram of hardware counters and comparators:

Hardware

comparator A x 4 Set /reset A1

I010 A1

Hardware

 

Count

counter A

 

value A

Set /reset A4

I040 A4

Hardware

comparator B x 4 Set /reset B1

I050 B1

Hardware

 

Count

counter B

 

value B

Set /reset B4

I080 B4

7.Difference between software and hardware comparators (it is not applicable to DVP-SE):

3 - 126

Page 242
Image 242