DVP-ES2/EX2/SS2/SA2/SX2/SE Operation Manual - Programming

Device

Function

Set-point range

Explanation

No.

 

 

 

 

 

 

The proportion for

S3+1:

Proportional gain (KP)

0~30,000(%)

magnifying/minifying the error

 

 

 

between SV and PV.

 

 

 

 

 

 

 

The proportion for

 

Integration gain (KI)

0~30,000(%)

magnifying/minifying the integral

 

value (The accumulated error). For

S3+2:

 

 

 

 

control mode K0~K2, K5.

 

 

 

 

 

 

 

 

Integral time constant

0~30,000 (ms)

For control mode K10

 

(TI)

 

 

 

 

 

 

 

 

 

 

The proportion for

 

 

-30,000~30,000

magnifying/minifying the derivative

 

Derivative gain (KD)

value (The rate of change of the

 

(%)

S3+3:

 

process error). For control mode

 

 

 

 

 

K0~K2, K5.

 

 

 

 

 

Derivative time constant

-30,000~30,000

For control mode K10

 

(TD)

(ms)

 

 

 

 

 

 

 

 

0: Automatic control

 

 

1: Forward control (E = SV - PV).

 

 

2: Reverse control (E = PV - SV).

 

 

5: Automatic mode with MV upper/lower bound control.

S3+4:

Control mode

When MV reaches upper/lower bound, the

 

 

accumulation of integral value stops.

 

 

10: TI / TD mode with MV upper/lower bound control.

 

 

When MV reaches upper/lower bound, the

 

 

accumulation of integral value stops.

 

 

 

 

 

 

 

E = the error between SV and PV.

S3+5,

Tolerable range for error

0~

If S3 +5 is set as 5, when E is

between -5 and 5, E will be 0.

6:

(E), 32-bit

2,147,483,647

When S3 +5 = K0, the function will

 

 

 

 

 

 

not be enabled.

 

 

 

 

 

 

 

Ex: if S3+6 is set as 1,000, MV will

S3+7,

Upper bound of output

-2,147,483,648

be 1,000 when it exceeds 1,000.

~

S3+6 has to be bigger or equal to

8:

value (MV) , 32-bit

2,147,483,647

S3+7, otherwise the upper bound

 

 

 

 

 

 

and lower bound value will switch

 

 

 

 

3 - 244

Page 360
Image 360
Delta DVP-ES2/EX2/SS2/SA2/SX2/SE manual Proportion for