4 . Communications

Sent message:

 

Field Name

 

 

ASCII

 

STX

 

:

 

 

 

 

 

Slave Address

 

01

 

 

 

 

 

Command code

 

10

 

 

 

 

 

Starting Address Hi

 

06

 

 

 

 

 

Starting Address Lo

 

00

 

 

 

 

 

Number of Register Hi

 

00

 

 

 

 

 

Number of Register Lo

 

02

 

 

 

 

 

Byte Count

 

04

 

 

 

 

 

Data Hi

 

00

 

 

 

 

 

Data Lo

 

0A

 

 

 

 

 

Data Hi

 

01

 

 

 

 

 

Data Lo

 

02

 

 

 

 

 

Error Check (LRC)

 

D6

 

 

 

 

 

END 1

 

0D(Hex)

 

 

 

 

 

END 0

 

0A(Hex)

 

 

 

 

PLC→PC “: 01 10 06 00 00 02 E7 CR LF”

 

Feedback message:

 

 

Field Name

 

 

ASCII

 

STX

 

 

3A

 

 

 

 

 

 

Slave Address

 

 

01

 

 

 

 

 

 

Command code

 

 

10

 

 

 

 

 

 

Starting Address Hi

 

 

06

 

 

 

 

 

 

Starting Address Lo

 

 

00

 

 

 

 

 

 

Number of Registers Hi

 

 

00

 

 

 

 

 

 

Number of Registers Lo

 

 

02

 

 

 

 

 

 

Error Check (LRC)

 

 

E7

 

 

 

 

 

 

END 1

 

 

0D (Hex)

 

 

 

 

 

 

END 0

 

 

0A (Hex)

 

 

 

 

 