4.5.6 Command Code: 15, Force ON/OFF multiple contacts

Max contacts/coils available for Force ON/OFF: 255

Example: Set Coil Y007…Y000 = 1100 1101, Y011…Y010 = 01.

PC→PLC

“: 01 0F 05 00 00 0A 02 CD 01 11 CR LF”

Sent message:

 

 

 

Field Name

 

 

ASCII

 

STX

 

 

 

:

 

 

 

 

 

Slave Address

 

01

 

 

 

 

 

Command code

 

0F

 

 

 

 

 

Coil Address Hi

 

05

 

 

 

 

 

Coil Address Lo

 

00

 

 

 

 

 

Quantity of Coils Hi

 

00

 

 

 

 

 

Quantity of Coils Lo

 

0A

 

 

 

 

 

Byte Count

 

02

 

 

 

 

 

Force Data Hi

 

CD

 

 

 

 

 

Force Data Lo

 

01

 

 

 

 

 

Error Check (LRC)

 

11

 

 

 

 

 

END 1

 

0D (Hex)

 

 

 

 

 

END 0

 

0A (Hex)

 

 

 

 

 

PLC→PC

“: 01 0F 05 00 00 0A E1 CR LF”

 

Feedback message:

 

 

 

Field Name

 

 

ASCII

 

STX

 

 

 

:

 

 

 

 

 

 

Slave Address

 

 

01

 

 

 

 

 

 

Command code

 

 

0F

 

 

 

 

 

 

Register T0 Address Hi

 

 

05

 

 

 

 

 

 

Register T0 Address Lo

 

 

00

 

 

 

 

 

 

Preset Data Hi

 

 

00

 

 

 

 

 

 

Preset Data Lo

 

 

0A

 

 

 

 

 

 

Error Check (LRC)

 

 

E1

 

 

 

 

 

 

END 1

 

 

0D (Hex)

 

 

 

 

 

 

END 0

 

 

0A (Hex)

 

 

 

 

 

 

4.5.7Command Code: 16, Set content of multiple registers Example: Set register T0 to 00 0A , T1 to 01 02 .