DVP - ES2/EX2/SS2/SA2/SX2/SE Operation Manual - Programming

Master PLC

Preset value

Slave PLC

Preset value

 

 

 

 

D1480 ~ D1495

K5,000

D100 ~ D115 of Slave ID#1

K5,000

D1496 ~ D1511

K1,000

D200 ~ D215 of Slave ID#1

K1,000

D1512 ~ D1527

K6,000

D100 ~ D115 of Slave ID#2

K6,000

D1528 ~ D1543

K2,000

D200 ~ D215 of Slave ID#2

K2,000

d)Up to16 Slaves can be accessed through PLC LINK. For allocation of D100 ~ D115 and D200 ~ D215 in each Slave PLC, please refer to the tables of Special M and Special D of this function in previous pages.

12.Example 2: Conncet DVP-PLC with VFD-M inverter and control the RUN, STOP, Forward operation, Reverse operation through PLC LINK.

a)Write the ladder diagram program into Master PLC (ID#17)

M1002

MOV

K17

D1121

Master ID#

MOV

H86

D1120

COM2 communication protocol

SET

MOV

MOV

MOV

MOV

MOV

M1120 Retain communication setting

K6

D1434

Data length to be read

K2

D1450

Data length to be witten

H2100

D1355

Starting reference of data

to be read on Slave

 

 

H2000

D1415

Starting reference of data

to be written on Slave

 

 

K1

D1399

ID# of the starting Slave

SET

M1355

Set the Slave to be linked manually

SET

M1360

Link Slave ID#1

X1

Auto mode

M1351

M1350

Enable EASY PLC LINK

END

b)M1355 = ON. Set the Slave to be linked manually by M1360~M1375. Set ON M1360 to link Slave ID#1.

c)Address H2100-H2105 maps to registers D1480-D1485 of PLC. When X1 = ON, PLC LINK executes, and the data in H2100-H2105 will be displayed in D1480-D1485.

d)Address H2000-H2001 maps to registers D1496-D1497 of PLC. When X1 = ON, PLC LINK executes, and the parameter in H2000-H2001 will be specified by D1496-D1497.

2 - 82

Page 114
Image 114
Delta DVP-ES2/EX2/SS2/SA2/SX2/SE manual Set Mov