3. Instruction Set

MOV K20E0 D10F0

E0 = 8 F0 = 14

 

20 + 8 = 28 10 + 14 = 24

 

Transmission K28

D24

The opposite diagram E, F index register modification refers to the content in the operand changes with the contents in E and F.

For example, E0 = 8 and K20E0 represents constant K28 (20 + 8). When the condition is true, constant K28 will be transmitted to register D24.

Devices modifiable: P, X, Y, M, S, KnX, KnY, KnM, KnS, T, C, D.

E and F can modify the devices listed above but cannot modify themselves and Kn., e.g. K4M0E0 is valid and K0E0M0 is invalid. Grey columns in the table of operand at the beginning page of each application instruction indicate the operands modifiable by E and F.

If you need to modify device P, I, X, Y, M, S, KnX, KnY, KnM, KnS, T, C and D by applying E, F, you have to select a 16-bit register, i.e. you can designate E or F.

3 - 2 3

Page 139
Image 139
Delta DVP-ES2/EX2/SS2/SA2/SX2/SE manual Instruction Set