DVP - ES2EX2/SS2/SA2/SX2/SE Operation Manual - Programming

6.Restrictions on diverging sequence: Please refer to section 5.5 for examples

a)Max. 8 step points could be used for single divergence sequence.

b)Max. 16 step points could be used for the convergence of multiple diverted sequences.

c)Users can assign a step in the sequence to jump to any step in another sequence.

7.Reset step points and disable outputs

a)Use the ZRST instruction to reset (turn off) a specified step sequence..

b)Set ON the flag M1034 to disable Y outputs.

8.Latched step:

The ON/OFF status of the latched step will be memorized when the power of the PLC is switched off. When the PLC is powered up again, PLC will resume the status before power-off and executes from the interrupted point. Please be aware of the area for the latched steps.

9.Special auxiliary relays and special registers: For more details please refer to 5.6 IST Instruction.

Device

Description

 

 

M1040

Disabling step transition.

 

 

M1041

Step transition start. Flag for IST instruction.

 

 

M1042

Enabling pulse operation. Flag for IST instruction.

 

 

M1043

Zero return completed. Flag for IST instruction.

 

 

M1044

Zero point condition. Flag for IST instruction.

 

 

M1045

Disabling “all output reset” function. Flag for IST instruction.

 

 

M1046

Indicating STL status. M1046 = ON when any step is ON

 

 

M1047

Enabling STL monitoring

 

 

D1040

No. of the 1st step point which is ON.

 

 

D1041

No. of the 2nd step point which is ON

 

 

D1042

No. of the 3rd step point which is ON.

 

 

D1043

No. of the 4th step point which is ON

 

 

D1044

No. of the 5th step point which is ON.

 

 

D1045

No. of the 6th step point which is ON

 

 

D1046

No. of the 7th step point which is ON.

 

 

D1047

No. of the 8th step point which is ON

 

 

5 - 10

Page 632
Image 632