3. Instruction Set

API

224~

230

Mnemonic

Operands

Function

 

 

 

 

 

D

LD

 

 

Contact Type Comparison

 

 

 

 

 

Controllers

ES2/EX2 SS2 SA2 SX2

SE

Type

Bit Devices

 

 

 

 

 

Word devices

 

 

 

 

 

Program Steps

OP

X

Y

M

S

K

H KnX KnY KnM KnS T

C D E

F

LD: 5 steps

S1

 

 

 

 

*

 

*

*

*

*

*

*

 

*

*

*

 

*

DLD: 9 steps

S2

 

 

 

 

*

*

*

*

*

*

*

*

*

*

*

 

 

 

 

 

 

 

 

 

 

 

PULSE

 

 

 

 

 

16-bit

 

32-bit

ES2/EX2

SS2

SA2

SX2

ES2/EX2

SS2

SA2

SX2

ES2/EX2

SS2

SA2

SX2

SE

SE

SE

Operands:

S1: Source device 1 S2: Source device 2

Explanations:

1.This instruction compares the content in S1 and S2. Take API224 (LD=) for example, if the result is “=”, the continuity of the instruction is enabled. If the result is “≠”, the continuity of the instruction is disabled.

2.LD(: =, >, <, <>, ≤, ≥) instruction is used for direct connection with left hand bus bar.

API No.

16 -bit

32 -bit

Continuity

Discontinuity

instruction

instruction

condition

condition

 

224

LD

DLD

S1S2

S1S2

225

LD

DLD

S1S2

S1S2

226

LD

DLD

S1S2

S1S2

228

LD<>

DLD<>

S1S2

S1S2

229

LD<=

DLD<=

S1S2

S1S2

230

LD>=

DLD>=

S1S2

S1S2

3.When the MSB (16-bit instruction: b15, 32-bit instruction: b31) of S1 and S2 is 1, the comparison value will be viewed as a negative value in comparison.

4.When 32-bit counters (C200 ~ C254) are used in this instruction, make sure to adopt 32-bit instruction (DLD). If 16-bit instruction (LD) is adopted, a “program error” will occur and the ERROR indicator on the MPU panel will flash.

Program Example:

1.When the content in C10 = K200, Y20 = ON.

2.When the content in D200 > K-30 and X1 = ON, Y21 = ON and latched.

LD=

K200

C10

 

Y20

 

X1

LD<= D200 K-30

SET Y21

3 - 4 7 1