DVP - ES2/EX2/SS2/SA2/SX2/SE Operation Manual - Programming
zThis instruction can be used many times in user program, but only one instruction will be activated at a time. For example, if Y0 is currently activated, other instructions use Y0 won’t be executed. Therefore, instructions first activated will be first executed.
zAfter activating the instruction, all parameters cannot be modified unless instruction is OFF.
3.Associated Flags:
M1029 CH0 (Y0, Y1) pulse output execution completed.
M1102 CH1 (Y2, Y3) pulse output execution completed
M1078 CH0 (Y0, Y1) pulse output pause (immediate)
M1104 CH1 (Y2, Y3) pulse output pause (immediate)
M1108 CH0 (Y0, Y1) pulse output pause (ramp down).
M1110 CH1 (Y2, Y3) pulse output pause (ramp down)
M1156 Enabling the mask and alignment mark function on I400/I401(X4) corresponding to Y0.
M1158 Enabling the mask and alignment mark function on I600/I601(X6) corresponding to Y2.
M1305 Reverse Y1 pulse output direction in high speed pulse output instructions M1306 Reverse Y3 pulse output direction in high speed pulse output instructions M1347
M1524
M1534 Enable
M1535 Enable
M1538 Indicating pause status of CH0 (Y0, Y1)
M1540 Indicating pause status of CH1 (Y2, Y3)
4.Special D registers:
D1030 Low word of the present value of Y0 pulse output
D1031 High word of the present value of Y0 pulse output D1336 Low word of the present value of Y2 pulse output
D1337 High word of the present value of Y2 pulse output
D1340 Start/end frequency of the 1st group pulse output CH0 (Y0, Y1)
D1352 Start/end frequency of the 2nd group pulse output CH1 (Y2, Y3)
D1343 Ramp up/down time of the 1st group pulse output CH0 (Y0, Y1)
D1353 Ramp up/down time of the 2nd group pulse output CH1 (Y2, Y3)
D1348: CH0(Y0, Y1) pulse output. When M1534 = ON, D1348 stores the
D1349: CH1(Y2, Y3) pulse output. When M1535 = ON, D1349 stores the
3 - 372