2. Programming Concepts

Binary

Octal

Decimal (K)

BCD

Hexadecimal (H)

(BIN)

(OCT)

(DEC)

(Binary Code Decimal)

(HEX)

 

 

 

 

 

For PLC

No. of X, Y

Costant K, No. of

For DIP Switch and 7-

Constant H

internal

registers M, S, T, C,

relay

segment display

operation

D, E, F, P, I devices

 

 

 

 

1101

15

13

0011

D

 

 

 

 

 

1110

16

14

0100

E

 

 

 

 

 

1111

17

15

0101

F

 

 

 

 

 

10000

20

16

0110

10

 

 

 

 

 

10001

21

17

0111

11

 

 

 

 

 

2.8M Relay

The types and functions of special auxiliary relays (special M) are listed in the table below. Care should be taken that some devices of the same No. may bear different meanings in different series MPUs. Special M and special D marked with “*” will be further illustrated in 2.13. Columns marked with “R” refers to “read only”, “R/W” refers to “read and write”, “-“ refers to the status remains unchanged and “#” refers to that system will set it up according to the status of the PLC.

Special

 

ES2

SS2

SA2

SX2

OFF

STOP

RUN

Attrib.

Latch

Default

Function

Ø

Ø

Ø

M

 

EX2

 

 

 

ON

RUN

STOP

 

-ed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M1000*

Monitor normally open contact

OFF

ON

OFF

R

NO

OFF

 

 

 

 

 

 

 

 

 

 

 

 

M1001*

Monitor normally closed contact

ON

OFF

ON

R

NO

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

Enable single positive pulse at the

 

 

 

 

 

 

 

 

 

 

M1002*

moment when RUN is activate (Normally

OFF

ON

OFF

R

NO

OFF

 

OFF)

 

 

 

 

 

 

 

 

 

 

 

Enable single negative pulse at the

 

 

 

 

 

 

 

 

 

 

M1003*

moment when RUN is activate (Normally

ON

OFF

ON

R

NO

ON

 

ON)

 

 

 

 

 

 

 

 

 

 

M1004*

ON when syntax errors occur

OFF

OFF

-

R

NO

OFF

 

 

 

 

 

 

 

 

 

 

 

 

M1008*

Watchdog timer (ON: PLC WDT time out)

OFF

OFF

-

R

NO

OFF

 

 

 

 

 

 

 

 

 

 

 

 

M1009

Indicate LV signal due to 24VDC

OFF

-

-

R

NO

OFF

insufficiency

 

 

 

 

 

 

 

 

 

 

 

M1011*

10ms clock pulse, 5ms ON/5ms OFF

OFF

-

-

R

NO

OFF

 

 

 

 

 

 

 

 

 

 

 

 

M1012*

100ms clock pulse, 50ms ON / 50ms

OFF

-

-

R

NO

OFF

OFF

 

 

 

 

 

 

 

 

 

 

 

M1013*

1s clock pulse, 0.5s ON / 0.5s OFF

OFF

-

-

R

NO

OFF

 

 

 

 

 

 

 

 

 

 

 

 

M1014*

1 min clock pulse, 30s ON / 30s OFF

OFF

-

-

R

NO

OFF

 

 

 

 

 

 

 

 

 

 

 

 

M1015*

Enable high-speed timer

OFF

-

-

R/W

NO

OFF

 

 

 

 

 

 

 

 

 

 

 

 

M1016*

Indicate Year display mode of RTC.

OFF

-

-

R/W

NO

OFF

 

 

 

 

 

 

 

 

 

 

 

 

M1017*

±30 seconds correction on real time clock

OFF

-

-

R/W

NO

OFF

 

 

 

 

 

 

 

 

 

 

 

 

M1018

Flag for Radian/Degree, ON for degree

OFF

-

-

R/W

NO

OFF

 

 

 

 

 

 

 

 

 

 

 

 

2 - 1 7