DVP - ES2/EX2/SS2/SA2/SX2/SE Operation Manual - Programming

ASCII mode (M1143 = OFF)

When X0 = ON, MODRW instruction executes the function specified by Function Code 06 PLC Ö VFD-B, PLC sends: “01 06 2000 1770 52”

VFD-B Ö PLC, PLC receives: “01 06 2000 1770 52”

Registers for data to be sent (sending messages)

Register

 

Data

 

Descriptions

D1256

Low byte

‘0’

 

30 H

ADR 1

Device address of VFD-B:

D1256

High byte

‘1’

 

31 H

ADR 0

ADR (1,0)

 

 

 

 

 

 

D1257 Low byte

‘0’

 

30 H

CMD 1

Control parameter: CMD (1,0)

 

 

 

 

 

 

D1257

High byte

‘6’

 

36 H

CMD 0

 

 

 

 

 

 

 

 

 

D1258

Low byte

‘2’

 

32 H

 

 

 

 

 

 

 

 

 

D1258

High byte

‘0’

 

30 H

Data Address

 

 

 

 

 

 

 

D1259

Low byte

‘0’

 

30 H

 

 

 

 

 

 

 

 

 

 

 

D1259

High byte

‘0’

 

30 H

 

 

 

 

 

 

 

 

 

D1260

Low byte

‘1’

 

31 H

 

 

 

 

 

 

 

Data

H1770 = K6000.

D1260

High byte

‘7’

 

37 H

 

 

 

 

 

content

The content of register D50

D1261

Low byte

‘7’

 

37 H

 

 

 

 

 

 

 

D1261

High byte

‘0’

 

30 H

 

 

 

 

 

 

 

 

D1262 Low byte

‘5’

 

35 H

LRC CHK 1

Checksum: LRC CHK (0,1)

 

 

 

 

 

 

D1262 High byte

‘2’

 

32 H

LRC CHK 0

 

 

 

 

 

 

 

 

 

Registers for received data (responding messages)

Register

 

Data

Descriptions

D1070

Low byte

‘0’

 

30 H

ADR 1

 

 

 

 

 

 

D1070

High byte

‘1’

 

31 H

ADR 0

 

 

 

 

 

D1071 Low byte

‘0’

 

30 H

CMD 1

 

 

 

 

 

 

D1071

High byte

‘6’

 

36 H

CMD 0

 

 

 

 

 

 

D1072

Low byte

‘2’

 

32 H

 

 

 

 

 

 

 

D1072

High byte

‘0’

 

30 H

Data Address

 

 

 

 

 

D1073

Low byte

‘0’

 

30 H

 

 

 

 

 

 

 

 

D1073

High byte

‘0’

 

30 H

 

 

 

 

 

 

 

D1074

Low byte

‘1’

 

31 H

 

 

 

 

 

 

 

D1074

High byte

‘7’

 

37 H

Data content

 

 

 

 

 

D1075

Low byte

‘7’

 

37 H

 

 

 

 

 

 

 

 

D1075

High byte

‘0’

 

30 H

 

 

 

 

 

 

D1076 Low byte

‘6’

 

36 H

LRC CHK 1

 

 

 

 

 

D1076 High byte

‘5’

 

35 H

LRC CHK 0

 

 

 

 

 

 

3 - 348

Page 464
Image 464
Delta DVP-ES2/EX2/SS2/SA2/SX2/SE manual VFD-B Ö PLC, PLC receives 01 06 2000 1770