3. Instruction Set
3-439
API Mnemonic Operands Function
197
D CLLM Close loop position
control
Controllers
ES2/EX2 SS2 SA2
SE SX2
Bit Devices Word devices Program Steps Type
OP X Y M S K H KnX KnY KnM KnS T C D E F
S1 * *
S2 * * *
S3 * * *
D *
DCLLM: 17 steps
PULSE 16-bit 32-bit
ES2/EX2 SS2 SA2
SE SX2 ES2/EX2 SS2 SA2
SE SX2 ES2/EX2 SS2 SA2
SE SX2
Operands:
S1: Feedback source device S2: Target number of feedbacks S3: Target frequency of
output D: Pulse output device
Explanations:
1. The corresponding interrupt pointers of S1:
Source device X4 X6 C243 ~ C254
Associted outout Y0 Y2 Y0 Y2
No. of Interrupt pointer I40I60I010 I050
= 1: rising-edige triggered; = 0: falling-edge triggered
a) When S1 designates input points X and the pulse output reaches the target number of
feedbacks in S2, the output will continue to operate by the frequency of the last shift (end
frequency) until interrupts occur on input points X.
b) When S1 designates high speed counters and the pulse output reaches the target
number of feedbacks in S2, the output will continue to operate by the frequency of the
last shift (end frequency) until the feedback pulses reaches the target number.
c) S1 can be a high speed counter C or an input point X with external interrupt. If S1 is C,
DCNT instruction should be executed in advance to enable the high-speed counting
function, and EI instruction with I0x0 should be enabled for external interrupts. If S1 is X,
EI instruction with I0x0 should be enabled for external interrupts.
d) If S1 is specifed with counters, DHSCS instruction has to be programmed in user
program. Please refer to Program example 2 for details.
2. Range of S2: -2,147,483,648 ~ +2,147,483,647 (+ / - indicates the positive / negative rotation
direction). the present value of pulse output in CH0 (Y0, Y1) and CH1 (Y2, Y3) increases in
positive direction and decreases in negative direction. Registers storing present value of
pulse output: CH0(D1031 High, 1030 Low), CH1(D1337 High, D1336 Low)
3. If S3 is lower than 6Hz, the output will operate at 6Hz; if S3 is higher than 100kHz, the output
will operate at 100kHz.