DVP-ES2/EX2/SS2/SA2/SX2/SE Operation Manual - Programming

Receving data: (External equipment→PLC)

D120L D121L D122L D123L D124L D125L D126L

Registers for received data, starting from lower 8 bits of D120

Length = 7

Program Example 6: COM3 RS-485

1.Only 8-bit mode is supported. Communication format and speed are specified by lower 8 bits of D1109.

2.STX/ETX setting function (M1126/M1130/D1124~D1126) is not supported.

3.High byte of 16-bit data is not available. Only low byte is valid for data communication.

4.Write the data to be transmitted in advance into registers starting from D100 and set M1316 (COM3 sending request) as ON

5.When X10 = ON, RS instruction executes and PLC is ready for communication. D0 will then start to send out 4 data continuously. When data sending is over, M1318 will be automatically reset. (DO NOT apply RST M1318 in program). After approximate 1ms, PLC will start to receive 7 data and store the data in 7 consecutive registers starting from D20.

6.When data receiving is completed, M1318 will automatically be ON. When data processing on the received data is completed, M1318 has to be reset (OFF) and the PLC will be ready for communication again. However, DO NOT continuously execute RST M1318, i.e. it is

suggested to connect the RST M1318 instruction after the drive contact M1318.

M1002

 

 

Setting communication protocol as 9600,8,E,1

 

 

 

 

MOV

H87

D1120

 

 

 

 

 

 

 

SET

M1136

Retain communication protocol

 

 

 

 

 

 

 

 

MOV

K100

D1252

Set up communication time out as 100ms

 

 

 

 

Pulse for

 

 

 

sending request

Pulse

X0

Write transmitting data in advance

SET

M1316 Sending request

 

 

 

 

 

RS

D100

K4

D120

K7

 

 

 

 

 

 

M1318

 

 

 

 

 

 

 

 

 

 

Processing received data

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RST

M1318

Receiving completed and flag reset

 

 

 

 

 

 

3 - 210

Page 326
Image 326