DVP - ES2/EX2/SS2/SA2/SX2/SE Operation Manual - Programming

API

Mnemonic

Operands

Function

Controllers

166

TRD

P

 

 

Time read

 

 

 

 

ES2/EX2 SS2 SA2 SX2

 

 

 

 

 

 

SE

 

 

 

 

 

 

 

 

 

 

 

 

 

Type

Bit Devices

 

Word devices

 

 

 

 

Program Steps

 

OP

X

Y

M

S

K

H KnX KnY KnM KnS T

C

D

E

F TRD, TRDP: 3 steps

 

D

 

 

 

 

 

*

*

*

 

 

 

 

 

 

 

 

 

 

PULSE

 

 

16-bit

 

32-bit

 

 

 

 

 

 

 

SA2

 

 

 

SA2

SA2

 

 

 

 

 

 

 

ES2/EX2 SS2 SE SX2 ES2/EX2 SS2

SE

SX2 ES2/EX2 SS2 SE

SX2

Operand:

D: Current time of RTC (occupies 7 consecutive devices)

Explanations:

1.TRD instruction reads the 7 real-time data of RTC (year (A.D.), day(Mon.Sun.), month, day, hour, minute, second from D1319~D1313 and stores the read data in registers specified by D.

2.Only when power is on can RTCs of SS2 series perform the fuction of timing. The RTC data registers D1319~D1313 are latched. When power is resumed, the RTC will resume the stored time value before power down. Therefore, we suggest users modify the RTC value every time when power is ON.

3.RTCs of SA2/SE V1.0 ES2/EX2/SX2 V2.0 series can still operate for one or two weeks after the power is off (they vary with the ambient temperature). Therefore, if the machine has not operated since one or two weeks ago, please reset RTC.

4.D1319 only stores the 2-digit year in A.D. If 4-digit year data is required, please refer to Points to note below.

5.For relative flags and registers please refer to Points to note.

Program Example:

When X0 = ON, TRD instruction reads the current time of RTC to the specified register D0~D6. The content of D1318: 1 = Monday; 2 = Tuesday … 7 = Sunday.

X0

TRD

D0

Special D

Item

Content

 

 

 

D1319

Year (A.D.)

00~99

 

 

 

D1318

Day (Mon.~Sun.)

1~7

 

 

 

D1317

Month

1~12

 

 

 

D1316

Day

1~31

D1315

Hour

0~23

 

 

 

D1314

Minute

0~59

 

 

 

D1313

Second

0~59

 

 

 

 

Normal D

Item

 

 

 

D0

Year (A.D.)

 

 

 

D1

Day (Mon.~Sun.)

 

 

 

D2

Month

 

 

 

D3

Day

D4

Hour

 

 

 

D5

Minute

 

 

 

D6

Second

 

 

 

3 - 382