3. Instruction Set

PLC ÖVFD-B,PLC transmits: “01 10 2000 0002 04 1770 0012 EE 0C”

VFD-BÖPLC, PLC receives: ”01 10 2000 0002 4A08”

Registers for data to be sent (sending messages)

 

Register

Data

 

 

Descriptions

 

D1256 Low byte

01 H

Address

 

 

 

 

 

 

 

 

D1257 Low byte

10 H

Function

 

 

 

 

 

 

 

 

D1258 Low byte

20 H

Data Address

 

 

 

 

 

 

D1259 Low byte

00 H

 

 

 

 

 

 

 

 

 

 

 

 

D1260 Low byte

00 H

Number of Register

 

 

 

 

D1261 Low byte

02 H

 

 

 

 

 

 

 

 

 

 

 

D1262 Low byte

04 H

Byte Count

 

 

 

 

 

 

 

 

D1263 Low byte

17 H

Data

 

The content of D50: H1770 (K6000)

 

D1264 Low byte

70 H

content 1

 

 

 

 

 

 

 

 

 

 

 

D1265 Low byte

00 H

Data

 

The content of D51: H0012 (K18)

 

D1266 Low byte

12 H

content 2

 

 

 

 

 

 

 

 

 

 

D1262 Low byte

EE H

CRC CHK Low

 

 

 

 

 

D1263 Low byte

0C H

CRC CHK High

 

 

 

 

 

Registers for received data (responding messages)

 

 

 

 

 

 

 

 

Register

Data

 

 

Descriptions

 

D1070 Low byte

01 H

Address

 

 

 

 

 

 

 

D1071 Low byte

10 H

Function

 

 

 

 

 

 

 

 

D1072 Low byte

20 H

Data Address

 

 

 

 

 

 

D1073 Low byte

00 H

 

 

 

 

 

 

 

 

 

 

 

 

D1074 Low byte

00 H

Number of Register

 

 

 

 

D1075 Low byte

02 H

 

 

 

 

 

 

 

 

 

D1076 Low byte

4A H

CRC CHK Low

 

 

 

 

 

D1077 Low byte

08 H

CRC CHK High

 

 

 

 

 

 

Program example 12: COM1 (RS-232) / COM3 (RS-485), Function Code H10

1.Function code K16 (H10): Write in multiple Word devices. Up to 16 Words can be written. For PLC COM2 ASCII mode, only 8 words can be written.

2.PLC COM1/COM3 will not process the received data

3.Take the connection between PLC COM3 and VFD-B for example, the tables below explain the status when PLC COM3 writes multiple Words in VFD-B. (M1320 = OFF, ASCII mode) (M1320 = ON, RTU mode)

z If PLC applies COM1 for communication, the below program can be usable by changing:

1.D1109→D1036: communication protocol