DVP - ES2/SA2/SS2/SA2/SX2/SE Operation Manual - Programming

Mnemonic

Operands

Function

Program steps

 

 

 

 

SET

Y, M, S

Latches the ON

1~3

status

 

 

 

Controllers

ES2/EX2 SS2 SA2SE SX2

Explanations:

When the SET instruction is driven, its designated device will be ON and latched whether the SET instruction is still driven. In this case, RST instruction can be applied to turn off the device.

Program example:

 

 

 

 

 

Ladder Diagram:

 

 

Instruction:

Operation:

 

X0 Y0

 

 

LD

X0

Load NO contact X0

 

 

 

 

 

 

 

 

 

 

SET

 

Y1

 

ANI

Y0

Connect NC contact Y0 in series

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SET

Y1

Drive Y1 and latch the status

Mnemonic

Operands

Function

Program steps

 

 

 

 

RST

Y, M, S, T, C, D, E,

Resets contacts,

3

F

registers or coils

 

 

 

 

 

 

Controllers

ES2/EX2 SS2 SA2SE SX2

Explanations:

Device status when RST instruction is driven:

Device

Status

 

 

S, Y, M Coil and contact are set to OFF.

T, C Current value is cleared. Associated contacts or coils are reset .

D, E, F The content is set to 0.

Status of designated devices remains the same when RST instruction is not executed.

Program example:

 

 

 

 

 

Ladder diagram:

 

 

Instruction:

Operation:

 

X0

 

 

LD

X0

Load NO contact X0

 

 

 

 

 

 

 

 

RST

 

Y5

 

RST

Y5

Reset contact Y5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Mnemonic

Operands

Function

Program steps

 

 

 

 

MC/MCR

N0~N7

Master control

3

Start/Reset

 

 

 

Controllers

ES2/EX2 SS2 SA2SE SX2

Explanations:

MC is the master-control start instruction. When MC instruction executes, the program execution turns to the designated nest level and executes the instructions between MC and MCR. However, MCR is the master-control reset instruction placed at the end of the designated nest level and no drive contact is required before MCR. When MC/MCR is not active, devices and instructions

3 - 8

Page 124
Image 124
Delta DVP-ES2/EX2/SS2/SA2/SX2/SE manual Set, Latches the on Status Controllers, Device Status, Rst, Mc/Mcr