3 . Instruction Set

M1000

M1049

Y0 X2

ANS

T0

K100

S912

Y1 X3

ANS T1 K200 S920

X0 X2

Y0

Y0

X1 X3

Y1

Y1

M1048

Y2

X4

ANRP

1.M1048 and D1049 are valid only when M1049 = ON.

2.When Y0 = ON for more than 10 sec and the product fails to reach the front position X2, S912 = ON

3.When Y1 = ON for more than 10 sec and the product fails to reach the back position X3, S920= ON.

4.When backward switch X1 = ON and backward device Y1 = ON, Y1 will go OFF only when the product reaches the back position switch X3.

5.Y2 is ON when any alarm is enabled.

6.Whenever X4 is ON, 1 active alarm will be reset. If there are several active alarms, the reset will start from the alarm with the lowest number and then the alarm with second lower number, etc.