3. Instruction Set
3-111
API Mnemonic Operands Function
46
ANS Timed Annunciator Set
Controllers
ES2/EX2 SS2 SA2
SE SX2
Bit Devices Word devices Program Steps Type
OP X Y M S K H KnX KnY KnM KnS T C D E F
S *
m *
D *
ANS: 7 steps
PULSE 16-bit 32-bit
ES2/EX2 SS2 SA2
SE SX2 ES2/EX2 SS2 SA2
SE SX2 ES2/EX2 SS2 SA2
SE SX2
Operands:
S: Alarm timer m: Time setting D: Alarm
Explanations:
1. ANS instruction is used to drive the output alarm device in designated time.
2. Operand S valid range: T0~T183
Operand m valid range: K1~K32,767 (unit: 100 ms)
Operand D valid range: S912~S1023
3. Flag: M1048 (ON: Alarm is active), M1049 (ON: Alarm monitoring is enabled)
4. See ANR instruction for more information
Program Example:
If X3 = ON for more than 5 sec, alarm step relay S999 will be ON. S999 will remains ON after X3 is
reset. (T10 will be reset, present value = 0)
X3 ANS T10 K50 S999