3 . Instruction Set

API

Mnemonic

Operands

Function

Controllers

 

46

ANS

 

Timed Annunciator Set

ES2/EX2

SS2

SA2

SX2

 

SE

Type

Bit Devices

 

 

 

Word devices

 

 

 

 

Program Steps

 

OP

X

Y

M

S

K

H KnX KnY KnM KnS T

C D

E

F

ANS: 7 steps

 

 

S

 

 

 

 

 

 

 

 

 

*

 

 

 

 

 

 

 

 

m

 

 

 

 

*

 

 

 

 

 

 

 

 

 

 

 

 

 

D

 

 

 

*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PULSE

 

 

16-bit

 

 

 

 

32-bit

 

 

 

 

 

 

 

ES2/EX2

SS2

SA2

SX2

ES2/EX2

SS2

SA2

SX2

ES2/EX2

SS2

SA2

SX2

 

 

 

 

 

SE

SE

SE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operands:

S: Alarm timer m: Time setting D: Alarm

Explanations:

1.ANS instruction is used to drive the output alarm device in designated time.

2.Operand S valid range: T0~T183

Operand m valid range: K1~K32,767 (unit: 100 ms)

Operand D valid range: S912~S1023

3.Flag: M1048 (ON: Alarm is active), M1049 (ON: Alarm monitoring is enabled)

4.See ANR instruction for more information

Program Example:

If X3 = ON for more than 5 sec, alarm step relay S999 will be ON. S999 will remains ON after X3 is reset. (T10 will be reset, present value = 0)

X3

ANS T10 K50 S999

3 - 111

Page 227
Image 227
Delta DVP-ES2/EX2/SS2/SA2/SX2/SE manual ANS T10 K50 S999