3. Instruction Set

API

Mnemonic

Operands

Function

Controllers

74

SEGL

 

7-segment with Latch

ES2/EX2

SS2

SA2 SX2

 

 

 

SE

Type

Bit Devices

 

 

 

 

Word devices

 

 

 

Program Steps

OP

X

Y

M

S

K

H KnX KnY KnM KnS T

C D

E

F

SEGL: 7 steps

S

 

 

 

 

* *

*

*

*

*

* * * * *

 

D

 

*

 

 

 

 

 

 

 

 

 

 

 

 

 

n

 

 

 

 

*

*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PULSE

 

 

 

16-bit

 

32-bit

 

ES2/EX2

SS2

SA2

SX2

ES2/EX2

SS2

SA2

SX2

ES2/EX2

SS2

SA2

SX2

 

SE

SE

SE

Operands:

 

 

 

 

 

 

 

 

 

 

S: Source device storing the value to be displayed in 7-segment display

D: Output device for

 

7-segment display

 

 

 

 

 

 

 

 

 

 

n: Configuration setting of output signal (n = 0~7)

 

 

 

 

 

 

 

 

 

 

Explanations:

185.This instruction occupies 8 or 12 consecutive external output points starting from D for displaying the data of 1 or 2 sets of 4-digit 7-segment display. Every digit of the 7-segment display carries a “Drive” which converts the BCD codes into 7-segment display signal. The drive also carries latch control signals to retain the display data of 7-segment display.

186.n specifies the number of sets of 7-segment display (1 set or 2 sets ), and designates the positive / negative output of PLC and the 7-segment display.

187.When there is 1 set of 4-digit output, 8 output points will be occupied. When there are 2 sets of 4-digit output, 12 output points will be occupied

188.When the instruction is executed, the output terminals will be scanned circularly. When the drive contact goes from OFF to ON again during the execution of instruction, the scan will restart from the beginning of the output terminals.

189.Flag: When SEGL is completed, M1029 = ON for one scan cycle.

190.There is no limitation on the times of using this instruction in the program, however only one instruction is allowed to be executed at a time.

Program Example:

191.When X20 = ON, SEGL instruction executes and Y24~Y27 forms an output scan loop for

7-segment display. The value of D10 will be mapped to Y20~Y23, converted to BCD code and sent to the 1st set of 7-segment display. The value of D11 will be mapped to Y30~Y33, converted to BCD code and sent to the 2nd set of 7-segment display. If the values in D10 and D11 exceed 9,999, operational error will occur.

X20

SEGL D10 Y20 K4

3-191

Page 307
Image 307