6.When RS instruction is applied for communication between PLC and peripheral devices on COM2 RS-485, usually STX (Start of the text) and ETX (End of the text) have to be set into communication format. In this case, b8~10 of D1120 should be set to 1, so that users can set up STX/ETX as user-defined or system-defined by using M1126, M1130, and D1124~D1126. For settings of M1126 and M1130, please refer to the following table.

 

 

 

M1130

 

 

0

 

1

 

 

D1124: user defined

 

D1124: H 0002

 

0

D1125: user defined

 

D1125: H 0003

M1126

 

D1126: user defined

 

D1126: H 0000no setting

 

D1124: user defined

 

D1124: H 003A’:’

 

1

D1125: user defined

 

D1125: H 000DCR

 

 

D1126: user defined

 

D1126: H 000ALF

 

 

 

 

 

7.Example of setting communication format in D1120: Communication format:

Baud rate: 9600, 7, N, 2

STX : “: “

ETX1 : “CR”

ETX2 : “LF”

Check to the table in point 4 and the set value H788 can be referenced corresponding to the baud rate. Set the value into D1120.

b15

b0

D1120 0 0 0 0 0 1 1 1 1 0 0 0 1 0 0 0

0

7

8

8

N/A

 

 

 

M1002

MOV H788 D1120

When STX, ETX1 and ETX2 are applied, care should be taken on setting the ON/OFF status of M1126 and M1130.

8.D1250(COM1)D1253(COM3) communication error code:

Value

Error Description

H0001

Communication time-out

 

 

H0002

Checksum error

 

 

H0003

Exception Code exists

H0004

Command code error / data error

 

 

3 - 220