DVP - ES2/EX2/SS2/SA2/SX2/SE Operation Manual - Programming

Register

Data

Descriptions

D1077 low byte

FE H

CRC CHK Low

 

 

 

D1078 low byte

5C H

CRC CHK High

 

 

 

Program Example 3:

1.In the communication between PLC and VFD-B series AC motor drive (ASCII Mode, M1143 = OFF), executes Retry when communication time-out, data receiving error or parameter error occurs.

2.When X0 = ON, PLC will read the data of address H2100 in device 01(VFD-B) and stores the data in ASCII format in D1070 ~ D1085. PLC will automatically convert the data and store them in D1050 ~ D1055.

3.M1129 will be ON when communication time-out occurs. The program will trigger M1129 and send request for reading the data again.

4.M1140 will be ON when data receiving error occurs. The program will trigger M1140 and send request for reading the data again.

5.M1141 will be ON when parameter error occurs. The program will trigger M1141 and send request for reading the data again.

M1002

 

 

Set communication protocol as 9600, 8, E, 1

 

 

 

 

 

 

MOV

H87

D1120

 

 

 

 

 

 

 

 

 

 

SET

M1120

Retain communication protocol

 

 

 

 

 

 

 

 

 

 

 

 

MOV

K100

D1129

Set communication time-out as 100ms

 

 

 

 

 

 

X0

 

Sending request

 

 

 

 

 

 

SET

M1122

 

 

 

 

 

 

 

 

 

 

 

 

M1129

Retry when communication time-out occurs

M1140

Retry when data receiving error occurs

M1141

Retry when parameter error occurs

X0

MODRD K1

H2100

K 6

Receiving completed

Set communication instruction: Data length: 6 words

Data address: H2100

Device address: 01

M1127

M1129

The received ASCII data is stored in D1070-D1085 Handle received data and PLC converts the data and store them into

D1050-D1055 automatically.

RST

M1127

Reset M1127

RST

M1129

Reset M1129 (receiving timeout)

3 - 272