DVP-ES2/EX2/SS2/SA2/SX2/SE Operation Manual - Programming

Flag

Function

Action

 

In ASCII mode, M1131 = ON only when MODRD/RDST/MODRW

 

M1131

data is being converted to HEX.

 

Supported communication instructions:

 

 

 

 

MODRD / RDST / MODRW

 

 

 

 

 

MODRD/MODWR/MODRW data receiving error

 

M1140

Supported communication instructions:

 

 

MODRD / MODWR / MODRW

System

 

sets

 

 

 

MODRD/MODWR/MODRW parameter error

 

M1141

Supported communication instructions:

 

 

MODRD / MODWR/ MODRW

 

 

 

 

 

Data receiving error of VFD-A handy instructions.

 

M1142

Supported communication instructions:

 

 

FWD / REV / STOP / RDST / RSTEF

 

 

 

 

 

ASCII / RTU mode selection. ON : RTU mode, OFF: ASCII mode.

 

M1143

Supported communication instructions:

User sets

RS / MODRD / MODWR / MODRW (When M1177 = ON, FWD /

and resets

 

 

 

 

REV / STOP / RDST / RSTEF can also be applied.

 

 

 

 

M1161

8/16-bit mode. ON: 8-bit mode. OFF: 16-bit mode

 

Supported communication instructions: RS

 

 

 

 

 

 

 

Enable the communication instruction for Delta VFD series inverter.

User sets

M1177

ON: VFD-A (Default), OFF: other models of VFD

 

Supported communication instructions:

 

 

 

 

FWD / REV / STOP / RDST / RSTEF

 

 

 

 

Special register

Function

 

Delay time of data response when PLC is SLAVE in COM2, COM3

D1038

RS-485 communication, Range: 0~10,000. (Unit: 0.1ms).

By using EASY PLC LINK in COM2, D1038 can be set to send next

 

 

communication data with delay. (unit: one scan cycle)

 

 

 

Converted data for Modbus communication data processing. PLC

D1050~D1055

automatically converts the ASCII data in D1070~D1085 into Hex data

and stores the 16-bit Hex data into D1050~D1055

 

 

Supported communication instructions: MODRD / RDST

 

 

3 - 214

Page 330
Image 330
Delta DVP-ES2/EX2/SS2/SA2/SX2/SE manual Modrd / Rdst / Modrw, Modrd / Modwr / Modrw, Modrd / MODWR/ Modrw