DVP-ES2/EX2/SS2/SA2/SX2/SE Operation Manual - Programming

API Mnemonic

Operands

Function

Controllers

67

D

RAMP

Ramp variable

ES2/EX2

SS2

SA2 SX2

Value

 

 

SE

 

 

 

 

 

Type

Bit Devices

 

Word devices

 

 

 

 

 

Program Steps

 

OP

X

Y

M

S

K

H KnX KnY KnM KnS T

C

D

E

F

RAMP: 9 steps

 

 

S1

 

 

 

 

 

 

 

 

*

 

 

DRAMP: 17 steps

 

 

S2

 

 

 

 

 

 

 

 

*

 

 

 

 

 

 

D

 

 

 

 

 

 

 

 

*

 

 

 

 

 

 

n

 

 

 

 

*

*

 

 

*

 

 

 

 

 

 

 

 

 

 

 

 

PULSE

 

 

 

16-bit

 

 

32-bit

 

 

 

 

 

 

 

 

SA2

 

 

 

 

SA2

 

SA2

 

 

 

 

 

 

 

ES2/EX2 SS2 SE

SX2 ES2/EX2 SS2

SE

SX2 ES2/EX2 SS2

SE

SX2

Operands:

S1: Start of ramp signal S2: End of ramp signal D: Current value of ramp signal (occupies 2

consecutive devices) n: Times for scan (n: 1~32,767)

Explanations:

147.This instruction creates a ramp output. A ramp output linearity depends on a consistent scan time. Therefore, scan time has to be fixed before executing RAMP instruction.

148.When RAMP instruction is executed, the ramp signal will vary from S1 to S2. Current value of ramp signal is stored in D and D+1 stores the current number of accumulated scans. When ramp signal reaches S2, or when the drive contact of RAMP instruction turns OFF, the content in D varies according to the setting of M1026 which is explained later in Points to note.

149.When n specifies a D register, the value in D cannot be modified during the execution of the instruction. Please modify the content of D when the instruction is stopped.

150.When this instruction is applied with analog output function, Ramp start and Ramp stop function can be achieved.

Program example:

1.Before executing the instruction, first drive M1039 = ON to fix the scan time. Use MOV instruction to write the fixed scan time to the special data register D1039. Assume the scan time is 30ms and take the below program for example, n = K100, the time for D10 to increase to D11 will be 3 seconds (30ms × 100).

2.When X20 goes OFF, the instruction will stop its execution. When X10 goes ON again, the content in D12 will be reset to 0 for recalculation

3.When M1026 = OFF, M1029 will be ON to indicate the completion of ramp process and the content in D12 will be reset to the set value in D10.

4.Set the Start and End of ramp signal in D10 and D11. When X20 = ON, D10 increases towards D11, the current value of the variation is stored in D12 and the number of current scans is

stored in D13.

X20

RAMP D10 D11 D12 K100

3 - 170

Page 286