3. Instruction Set

Sending data: (PLC→External equipment)

D100L D101L D102L D103L

Source data register, starting from lower 8 bits of D100

Length = 4

Receving data: (External equipment→PLC)

D120L D121L D122L D123L D124L D125L D126L

Registers for received data, starting from lower 8 bits of D120

Length = 7

Points to note:

1.PLC COM1 RS-232:Associated flags (Auxiliary relays) and special registers (Special D) for communication instructions RS / MODRD

Flag

Function

Action

 

COM1 retain communication settings. Communication settings will be

 

 

reset (changed) according to the content in D1036 after every scan

 

 

cycle. Users can set ON M1138 if the communication protocol

User

 

requires to be retained. When M1138 = ON, communication settings

M1138

sets and

 

will not be reset (changed) when communication instructions are

resets

 

 

 

being processed, even if the content in D1036 is changed.

 

 

Supported communication instructions: RS / MODRW

 

 

 

 

 

COM1 ASCII / RTU mode selection, ON: RTU mode, OFF: ASCII

User

 

mode.

M1139

sets and

 

Supported communication instructions: RS / MODRW

resets

 

 

 

 

 

 

COM1 sending request. Before executing communication instructions,

 

 

users need to set M1312 to ON by trigger pulse, so that the data

User

M1312

sending and receiving will be started. When the communication is

sets and

system

 

completed, PLC will reset M1312 automatically.

 

resets

 

Supported communication instructions: RS / MODRW

 

 

 

 

 

COM1 data receiving ready. When M1313 is ON, PLC is ready for

 

M1313

data receiving

System

 

Supported communication instructions: RS / MODRW

 

 

 

 

3 - 2 11

Page 327
Image 327
Delta DVP-ES2/EX2/SS2/SA2/SX2/SE manual Points to note, Flag Function Action